Power cable 0,6/1 kV with Al conductors, PVC insulated and sheathed

1-AYKY

APPLICATION

In earth, ducts, on support brackets, in dry and wet conditions etc., where one does not expect mechanical damages and the cables are not exposed to the mechanical tensile strain. In urban networks, industrial plants, electric power plants and other electricity consumers and for connection of control devices in industry, traffic etc.

CERTIFICATES


CONSTRUCTION

  • Sheath
    PVC compound DMV 1
  • Bedding
    Extruded elastomere or plastomere compound or plastic tape
  • Conductors
    Al, class 1 or 2 according to EN 60228
  • Insulation
    PVC compound DIV 1

TEHNICAL CHARACTERISTICS

  • Standard
    PNE 34 7659-3, HD 603 S1
  • CPR class
    Eca
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Min.bending radius
    multi-core 12D
  • Core identification
    Acc. to HD 308 S2
  • Min. laying temperature
    -5°C
  • Max.operating temperature
    70°C
  • Max.short-circuit temperature
    160°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
4x10 RE 3,080 - - 19,1
4x16 RM/RE 1,910 - - 22,0
4x25 RM/RE 1,200 82 102 27,8
4x35 RM/RE 0,868 100 123 30,5
4x50 RE/SE 0,641 119 144 29,9
4x70 RE/SE 0,443 152 179 33,2
3x95+50 SM/RM(SM) 0,320/0,641 186 215 38,5
3x95+70 SM/RE 0,320/0,443 186 215 38,5
4x95 SM 0,320 186 215 40,0
3x120+50 SM/RM(SM) 0,253/0,641 216 245 41,0
3x120+70 SM/RE(RM) 0,253/0,443 216 245 43,0
3x120+70 SM/SM 0,253/0,443 216 245 40,0
4x120 SM 0,253 216 245 43,0
3x150+70 SM/RE(RM) 0,206/0,443 246 275 46,0
3x150+70 SM/SM 0,206/0,443 246 275 45,5
4x150 SM 0,206 246 275 48,0
3x185+95 SM/RM 0,164/0,320 285 313 50,5
3x185+95 SM/SM 0,164/0,320 285 313 49,5
4x185 SM 0,164 285 313 52,5
3x240+120 SM/RM 0,125/0,253 338 364 58,0
3x240+120 SM/SM 0,125/0,253 338 364 57,0
4x240 SM 0,125 338 364 60,0
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W