Power cable 0,6/1 kV with Cu conductors, PVC insulated and sheathed

1-CYKY

APPLICATION

In earth, ducts, on support brackets, in dry and wet conditions etc., where one does not expect mechanical damages and the cables are not exposed to the mechanical tensile strain. In urban networks, industrial plants, electric power plants and other electricity consumers and for connection of control devices in industry, traffic etc.

CERTIFICATES


CONSTRUCTION

  • Sheath
    PVC compound DMV 1
  • Bedding
    Extruded elastomere or plastomere compound or plastic tape
  • Conductors
    Cu, class 1 or 2 according to EN 60228
  • Insulation
    PVC compound DIV 1

TEHNICAL CHARACTERISTICS

  • Standard
    PNE 34 7659-3, HD 603
  • CPR class
    Eca
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Core identification
    acc. to HD 308 S2
  • Min. bending radius
    multicore - 12D
  • Min. laying temperature
    -5°C
  • Max. operating temperature
    70°C
  • Max. short-circuit temperature
    160°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
4x10 RE 1,830 59 78 19,1
4x16 RM/RE 1,150 78 107 22,0
4x25 RM/RE 0,727 105 132 27,8
4x35 RM/RE 0,524 129 159 30,5
4x50 RE/SE 0,387 157 188 29,9
4x70 RE/SE 0,268 199 232 33,2
3x95+50 SM/RM(SM) 0,193/0,387 246 280 38,5
3x95+70 SM/RE 0,193/0,268 246 280 38,5
4x95 SM 0,193 246 280 40,0
3x120+50 SM/RM(SM) 0,153/0,387 285 318 41,0
3x120+70 SM/RE(RM) 0,153/0,268 285 318 43,0
3x120+70 SM/SM 0,153/0,268 285 318 40,0
4x120 SM 0,153 285 318 43,0
3x150+70 SM/RE(RM) 0,124/0,268 326 359 46,0
3x150+70 SM/SM 0,124/0,268 326 359 45,5
4x150 SM 0,124 326 359 48,0
3x185+95 SM/RM 0,0991/0,193 374 406 50,5
3x185+95 SM/SM 0,0991/0,193 374 406 49,5
4x185 SM 0,0991 374 406 52,5
3x240+120 SM/RM 0,0754/0,153 445 473 58,0
3x240+120 SM/SM 0,0754/0,153 445 473 57,0
4x240 SM 0,0754 445 473 60,0
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W