Power cable 0,6/1 kV with Al conductors, PVC insulated and sheathed, with concentric conductor

AMCMK

APPLICATION

Distribution power cable for static outdoor application (with protection against direct UV-irradiation), in ground, within facilities, in cable canals, in concrete, in conditions where there is a danger of possible mechanical damages, but where the cable is not exposed either to systematic mechanical stress or heavier tensile strain. Used in electric power plants, transformer stations, industrial plants, metropolitan networks and other electric plants. Concentric conductor can be used as neutral, protective or earth connection, and in situations where the insulation might be roughly damaged by some metal object, it acts as protection against contact voltage. Corrugated, concentric conductor construction enables establishing of several cable connections without cutting of conductor.

CERTIFICATES


CONSTRUCTION

  • Sheath
    PVC compound, type DMV 9
  • Bedding
    Extruded elastomere or plastomere compound or plastic tape
  • Conductors
    Al conductors, class 1 or 2 according to EN 60228
  • Insulation
    PVC compound, type DIV 6

TEHNICAL CHARACTERISTICS

  • Standard
    SFS 4880, HD 603 S1, p.3F
  • CPR class
    Eca
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Core identification
    According to HD 308 S2
  • Bending radius (min)
    12xD
  • Min. laying temperature
    -10°C
  • Max. conductor temperature
    60°C
  • Max. short-circuit temperature
    160°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.) Metal weight Cable weight (approx.)
mm2 Ω/km A A mm kg/km kg/km
3x16/10 RE/RM 1,910 62 78 20,3 139,2 443
3x25/16 RM/SM 1,200 77 100 23,9 217,5 632
3x35/16 SM 0,868 95 125 25,3 304,5 711
3x50/16 SM 0,641 117 150 28,3 435 896
3x70/21 SM 0,443 148 185 31,5 609 1173
3x95/29 SM 0,320 180 220 35,8 826,5 1566
3x120/41 SM 0,253 209 255 38,5 1044 1955
3x150/41 SM 0,206 240 280 42,4 1305 2310
3x185/57 SM 0,164 274 330 47,5 1609,5 2905
3x240/72 SM 0,125 323 375 53,1 1088 3692
3x300/88 SM 0,100 372 430 58,4 2610 4540
4x16/10 RE/RM 1,910 62 78 22,7 185,6 525
4x25/16 RM/SM 1,200 77 100 26,6 290 752
4x35/16 SM 0,868 95 125 28,8 406 842
4x50/16 SM 0,641 117 150 23,5 580 1093
4x70/21 SM 0,443 148 185 36,1 812 1434
4x95/29 SM 0,320 180 220 41 1102 1914
4x120/41 SM 0,253 209 255 44,5 1392 2387
4x150/41 SM 0,206 240 280 48,6 1740 2855
4x185/57 SM 0,164 274 330 53,2 5146 3531
4x240/72 SM 0,125 323 375 59,7 2784 4525
4x300/88 SM 0,100 372 430 65,5 3480 5565
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W