Power cable 0,6/1 kV with Al conductors, XLPE insulated and PVC sheathed

ARE4R

APPLICATION

In earth, ducts, on support brackets, in dry and wet conditions etc., where one does not expect mechanical damages and the cables are not exposed to the mechanical tensile strain. In urban networks, industrial plants, electric power plants and other electricity consumers and for connection of control devices in industry, traffic etc., where fire prevention safety measures are requested, for eleveted electricity and thermic strains.

CERTIFICATES


CONSTRUCTION

  • Sheath
    PVC compound Rz quality, gray
  • Conductors
    Al, class 2 according to EN 60228
  • Insulation
    XLPE compound, E4 quality

TEHNICAL CHARACTERISTICS

  • Standard
    CEI 20-13, IEC 60502-1
  • CPR class
    Eca
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Core identification
    Acc. to HD 308 S2
  • Bending radius (min)
    15D
  • Max. working temperature
    90°C
  • Min. temp. for cable laying
    -15°C
  • Max. short-circuit temperature
    250°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Outer diam. (approx.) Cable weight (approx.) Current capacity burried pipe, 20°C Current capacity burried pipe, 20°C Current capacity burried, 20°C Current capacity burried, 20°C Current capacity in pipe in air, 30°C Current capacity in air, 30°C
mm2 Ω/km mm kg/km K=1,5
A
K=1
A
K=1,5
A
K=1
A
A A
1x16 RM 1,910 10,0 150 70 75 89 98 64 70
1x25 RM 1,200 11,7 185 88 95 110 119 88 102
1x35 RM 0,868 13,0 220 106 115 131 141 110 136
1x50 RM 0,641 14,7 280 124 134 154 167 131 164
1x70 RM 0,443 16,6 320 160 173 189 204 175 218
1x95 RM 0,320 18,6 460 181 196 226 245 209 261
1x120 RM 0,253 20,5 570 220 238 256 277 250 310
1x150 RM 0,206 22,8 670 231 250 289 313 280 350
1x185 RM 0,164 25,0 810 278 300 324 350 334 415
1x240 RM 0,125 27,9 1025 306 331 382 413 392 490
1x300 RM 0,100 30,7 1205 370 400 420 454 - 567
1x400 RM 0,0778 35,0 1660 417 450 474 511 - 665
1x500 RM 0,0605 38,6 1940 464 505 535 578 - 765
1x630 RM 0,0469 43,1 2460 537 580 598 646 - 880
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W