Power cable 0,6/1 kV with Al conductors, XLPE insulated and HFFR sheathed

ARG16M16

APPLICATION

In earth, ducts, on support brackets, in dry and wet conditions etc., where one does not expect mechanical damages and the cables are not exposed to the mechanical tensile strain. In urban networks, industrial plants, electric power plants and other electricity consumers and for connection of control devices in industry, traffic etc., where fire prevention safety measures are requested, for eleveted electricity and thermic strains.

CERTIFICATES


CONSTRUCTION

  • Sheath
    LS0H compound M16 quality, green
  • Conductors
    Al, class 2 according to EN 60228
  • Insulation
    XLPE compound

TEHNICAL CHARACTERISTICS

  • Standard
    CEI 20-13
  • CPR class
    Cca-s1,d1,a1
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Bending radius (min)
    6D
  • Max. working temperature
    90°C
  • Min. temp. for cable laying
    -15°C
  • Max. short-circuit temperature
    250°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Outer diam. (approx.) Cable weight (approx.) Current capacity burried pipe, 20°C Current capacity burried pipe, 20°C Current capacity burried, 20°C Current capacity burried, 20°C Current capacity in pipe in air, 30°C Current capacity in air, 30°C Average sheath thickness Average insulation thickness
mm2 Ω/km mm kg/km K=1,5
A
K=1
A
K=1,5
A
K=1
A
A A mm mm
1x16 RM 1,910 9,1 109 70 75 89 98 64 70 1,4 0,7
1x25 RM 1,200 10,7 151 88 95 110 119 88 102 1,4 0,9
1x35 RM 0,868 11,7 185 106 115 131 141 110 134 1,4 0,9
1x50 RM 0,641 13,0 230 124 134 154 167 131 164 1,4 1,0
1x70 RM 0,443 14,9 315 160 173 189 204 175 218 1,4 1,1
1x95 RM 0,320 16,6 405 181 196 226 245 209 261 1,5 1,1
1x120 RM 0,253 28,5 510 220 238 256 277 250 310 1,5 1,2
1x150 RM 0,206 20,4 620 231 250 289 313 280 350 1,6 1,4
1x185 RM 0,164 22,6 750 278 300 324 350 334 415 1,6 1,6
1x240 RM 0,125 25,2 955 306 331 382 413 392 490 1,7 1,7
1x300 RM 0,100 27,9 1150 370 400 420 454 - 567 1,8 1,8
1x400 RM 0,0778 31,4 1520 417 450 474 512 - 665 1,9 2,0
1x500 RM 0,0605 34,9 1850 464 505 535 578 - 765 2,0 2,2
1x630 RM 0,0469 39,8 2415 537 580 598 646 - 880 2,2 2,4
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W