AT-N05VV-U (YM)

Low voltage (300/500 V) PVC insulated and sheathed installation cable

AT-N05VV-U (YM)

APPLICATION

Installation cable suitable for household and industrial usage. Laid on or under plaster, in walls or concrete, without special mechanical protection, but not in dry or pre-stressed concrete. Suitable for dry, same as damp or wet environment; for internal or external application (only if the cable is protected against direct sunlight.

CERTIFICATES


CONSTRUCTION

  • Sheath
    PVC compound TM1
  • Bedding
    PVC or EPDM compound
  • Conductors
    Cu conductors, class 1 according to EN 60228
  • Insulation
    PVC compound TI1

TEHNICAL CHARACTERISTICS

  • Standard
    ÖVE E 8242, IEC 60227-4
  • CPR class
    Eca
  • Test voltage
    2 kV
  • Rated voltage
    300/500 V
  • Core identification
    According to HD 308 S2
  • Bending radius (min)
    6xD
  • Max. conductor temperature
    +70°C
  • Max. short-circuit temperature
    +160°C
Nominal cross-section Max. Resistance at 20°C Current capacity in air Outer diam. (approx.) Metal weight Cable weight (approx.)
mm2 Ω/km A mm kg/km kg/km
2x1,5 12,1 17,5 8,2 28,8 123
2x2,5 7,41 24 9,5 48 167
2x4 4,61 32 11,2 76,8 227
2x6 3,08 41 12,3 115,2 288
2x10 1,830 57 15,0 192 470
2x16 1,150 76 17,1 307,2 703
2x25 0,727 101 20,5 480 1028
2x35 0,524 125 22,6 672 1133
3x1,5 12,1 17,5 8,5 43,2 142
3x2,5 7,41 24 10,0 72 196
3x4 4,61 32 11,8 115,2 272
3x6 3,08 41 13,0 172,8 365
3x10 1,830 57 15,9 288 576
3x16 1,150 76 18,1 460,8 872
3x25 0,727 101 22,2 720 1309
3x35 0,524 125 24,5 1008 1462
4x1,5 12,1 17,5 9,8 57,6 170
4x2,5 7,41 24 11,1 96 238
4x4 4,61 32 13,7 153,6 346
4x6 3,08 41 14,7 230,4 467
4x10 1,830 57 17,4 384 715
4x16 1,150 76 19,8 614,4 1089
4x25 0,727 101 24,3 960 1645
4x35 0,524 125 26,9 1344 1825
5x1,5 12,1 17,5 10,6 72 199
5x2,5 7,41 24 12,0 120 282
5x4 4,61 32 14,2 192 430
5x6 3,08 41 15,7 288 558
5x10 1,830 57 18,8 480 862
5x16 1,150 76 22,1 768 1341
5x25 0,727 101 26,7 1200 2002
5x35 0,524 125 30,4 1680 2276
7x1,5 12,1 17,5 12,5 100,8 235
7x2,5 7,41 24 12,8 168 349
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W