AXCMK

LV (0,6/1 kV) power cables with XLPE insulation and PVC sheath with concentric conductor

AXCMK

APPLICATION

In earth, ducts, on support brackets, in dry and wet conditions etc., where one does not expect mechanical damages and the cables are not exposed to the mechanical tensile strain. In urban networks, industrial plants, electric power plants and other electricity consumers and for connection of control devices in industry, traffic etc.

CONSTRUCTION

  • Sheath
    PVC compound
  • Bedding
    Extruded elastomere or plastomere compound or plastic tape
  • Conductor
    Al conductor
  • Insulation
    XLPE compound
  • Concentric conductor
    Cu wires with counter helix of Cu tape

TEHNICAL CHARACTERISTICS

  • Standard
    HD 603 S1-5D, SFS 4879
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Fire properties
  • Core identification
    acc. to HD 308 S2
  • Min bending radius
    Single-core 15D; multi-core 12D
  • Min. temperature laying
    -15°C
  • Max. operating temperature
    +90°C
  • Max. short-circuit temperature
    +250°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
3x35/16 SM 0,868 95 125 24,2
3x50/16 SM 0,641 117 150 26,7
3x70/21 SM 0,443 148 185 30,3
3x95/29 SM 0,320 180 220 34,0
3x120/41 SM 0,253 209 255 37,1
3x150/41 SM 0,206 240 280 41,0
3x185/87 SM 0,164 274 330 45,7
3x240/72 SM 0,125 323 375 50,6
4x35/16 SM 0,868 95 125 26,0
4x50/16 SM 0,641 117 150 28,9
4x70/21 SM 0,443 148 185 33,1
4x95/29 SM 0,320 180 220 37,2
4x120/41 SM 0,253 209 255 41,0
4x150/41 SM 0,206 240 280 45,2
4x185/87 SM 0,164 274 330 50,5
4x240/72 SM 0,125 323 375 56,0
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W