LV (0,6/1 kV) power cables with XLPE insulation and PE sheath

AXMK-PE

APPLICATION

In earth, ducts, on support brackets, in dry and wet conditions etc., where one does not expect mechanical damages and the cables are not exposed to the mechanical tensile strain. In urban networks, industrial plants, electric power plants and other electricity consumers and for connection of control devices in industry, traffic etc.

CERTIFICATES


CONSTRUCTION

  • Sheath
    PE compound
  • Bedding
    Extruded elastomere or plastomere compound or plastic tape
  • Conductors
    Al conductor
  • Insulation
    XLPE compound

TEHNICAL CHARACTERISTICS

  • Standard
    HD 603 S1, SFS 4879
  • CPR class
    Fca
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Max.bending radius
    Single-core 15D; multi-core 12D
  • Core identification
    Acc. to HD 308 S2
  • Min.laying temperature
    -15°C
  • Max.operating temperature
    +90°C
  • Max.short-circuit temperature
    +250°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
1x16 RE 1,910 - - 9,5
1x25 RE 1,200 106 114 11,0
1x35 RM 0,868 130 136 12,1
1x50 RM 0,641 161 162 13,6
1x70 RM 0,443 204 199 15,2
1x95 RM 0,320 252 238 16,8
1x120 RM 0,253 295 272 18,4
1x150 RM 0,206 339 305 20,2
1x185 RM 0,164 395 347 22,1
1x240 RM 0,125 472 404 24,5
1x300 RM 1,80 547 457 26,7
4x16 RE 1,910 - - 18,3
4x25 SM 1,200 102 112 21,1
4x35 SM 0,868 126 135 23,4
4x50 SM 0,641 149 158 26,4
4x70 SM 0,443 191 196 30,4
4x95 SM 0,320 234 234 34,1
4x120 SM 0,253 273 268 38,1
4x150 SM 0,206 311 300 42,1
4x185 SM 0,164 360 342 46,6
4x240 SM 0,125 427 398 52,2
4x300 SM 0,100 507 457 55,9
5x10 RE 3,080 - - 17,8
5x16 RE 1,910 - - 20,0
5x25 SM 1,200 102 112 22,9
5x35 SM 0,868 126 135 25,7
5x50 SM 0,641 149 158 30,1
5x70 SM 0,443 191 196 35,1
5x95 SM 0,320 234 234 38,1
5x120 SM 0,253 273 268 40,3
5x150 SM 0,206 311 300 47,4
5x185 SM 0,164 360 342 52,7
5x240 SM 0,125 427 398 59,4
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W