LV (0,6/1 kV) power cables with PVC insulation and PVC sheath

CABT

APPLICATION

In earth, ducts, on support brackets, in dry and wet conditions etc., where one does not expect mechanical damages and the cables are not exposed to the mechanical tensile strain. In urban networks, industrial plants, electric power plants and other electricity consumers and for connection of control devices in industry, traffic etc.

CERTIFICATES


CONSTRUCTION

  • Sheath
    PVC compound
  • Bedding
    Extruded elastomere or plastomere compound or plastic tape
  • Conductors
    Al rope
  • Insulation
    PVC compound

TEHNICAL CHARACTERISTICS

  • Standard
    БДС 16291, IEC 60502-1
  • CPR class
    Eca
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Min.bending radius
    Single-core 15D; multi-core 12D
  • Core identification
    Acc.to HD 308 S2
  • Min.laying temperature
    -5°C
  • Max.operating temperature
    +70°C
  • Max.short-circuit temperature
    +160°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
1x16 RM 1,910 - - 10,5
1x25 RM 1,200 87 106 12,0
1x35 RM 0,868 107 127 13,5
1x50 RM 0,641 131 151 15,0
1x70 RM 0,443 166 185 17,0
1x95 RM 0,320 205 222 19,0
1x120 RM 0,253 239 253 20,0
1x150 RM 0,206 273 284 22,0
1x185 RM 0,164 317 322 25,0
1x240 RM 0,125 378 375 28,0
1x300 RM 0,100 437 425 30,0
1x400 RM 0,0778 513 487 34,0
1x500 RM 0,0605 600 558 37,0
1x630 RM 0,0469 701 635 38,8
1x800 RM 0,0367 809 716 42,1
1x1000 RM 0,0291 916 796 46,6
3x70+35 SM/SM 0,443/0,868 152 179 33,0
3x95+50 SM/SM 0,320/0,641 186 215 37,8
3x120+70 SM/SM 0,253/0,443 216 245 40,4
3x150+70 SM/SM 0,206/0,443 246 275 44,9
3x185+95 SM/SM 0,164/0,320 285 313 49,0
3x240+120 SM/SM 0,125/0,253 338 364 55,2
3x16 RM/RE 1,910 - - 18,4
3x25 RM 1,200 82 102 21,7
3x35 RM 0,868 100 123 24,1
3x50 RM/SM 0,641 119 144 27,9
3x70 RM/SM 0,443 152 179 31,4
3x95 RM/SM 0,320 186 2115 35,9
4x16 RE/RM 1,910 - - 24,0
4x25 RM 1,200 82 102 25,0
4x35 RM 0,868 100 123 28,0
4x35 SM 0,868 100 123 28,0
4x50 SM 0,641 119 144 30,0
4x70 SM 0,443 152 179 35,0
4x95 SM 0,320 186 215 39,0
4x120 SM 0,253 216 245 41,0
4x150 SM 0,206 246 275 45,0
4x185 SM 0,164 285 313 49,0
4x240 SM 0,125 338 364 55,0
4x300 SM 0,100 400 419 59,0
5x16 RM 1,910 - - 23,4
5x25 RM 1,200 102 112 28,2
5x35 RM/SM 0,868 126 135 31,0
5x50 RM/SM 0,641 149 158 36,8
5x70 RM/SM 0,443 191 196 42,8
5x95 RM/SM 0,320 234 234 48,5
5x120 RM/SM 0,253 273 268 53,6
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W