Power cables 0,6/1 kV with Al conductors, PVC insulated and HDPE sheathed

EAY2Y

APPLICATION

In earth, ducts, on support brackets, in dry and wet conditions etc., where one does not expect mechanical damages and the cables are not exposed to the mechanical tensile strain. In urban networks, industrial plants, electric power plants and other electricity consumers and for connection of control devices in industry, traffic etc.

CERTIFICATES


CONSTRUCTION

  • Sheath
    HDPE compound
  • Bedding
    Extruded elastomere or plastomere compound or plastic tape
  • Conductors
    Al conductor
  • Insulation
    PVC compound

TEHNICAL CHARACTERISTICS

  • Standard
    HD 603 S1, ÖVE E 8200-603, IEC 60502-1
  • CPR class
    Fca
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Core identification
    acc. to HD 308 S2
  • Min. bending radius
    Single-core 15D, multi-core 12D
  • Min. laying temperature
    -5 °C
  • Max. operating temperature
    70 °C
  • Max. short-circuit temperature
    160 °C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
1x10 RM 3,08 - - 9,5
1x16 RM 1,910 - - 10,5
1x25 RM 1,200 87 106 12,1
1x35 RM 0,868 107 127 13,3
1x50 RM 0,641 131 151 15,1
1x70 RM 0,443 166 185 16,3
1x95 RM 0,320 205 222 18,4
1x120 RM 0,253 239 253 19,6
1x150 RM 0,206 273 284 21,8
1x185 RM 0,164 317 322 23,8
1x240 RM 0,125 378 375 26,7
1x300 RM 0,100 437 425 29,5
4x10 RE/RM 3,080 - - 18,8
4x16 RE/RM 1,910 - - 21,6
4x25 RM 1,200 82 102 25,2
4x35 RM 0,868 100 123 28,5
4x35 SM 0,868 100 123 26,0
4x50 SM 0,641 119 144 29,2
4x70 SM 0,443 152 179 32,5
4x95 SM 0,320 186 215 37,4
4x120 SM 0,253 216 245 40,7
4x150 SM 0,206 246 275 44,5
4x185 SM 0,164 285 313 49,2
4x240 SM 0,125 338 364 54,9
4x50 SE 0,641 119 144 27,7
4x70 SE 0,443 152 179 31,2
4x95 SE 0,320 186 215 35,1
4x120 SE 0,253 216 245 38,5
4x150 SE 0,206 246 275 42,7
4x185 SE 0,164 285 313 46,4
4x240 SE 0,125 338 364 51,8
5x10 RM 3,080 - - 21,1
5x16 RM 1,910 - - 23,7
5x25 RM 1,200 102 112 28,0
5x35 RM 0,868 126 135 31,7
3x50 RM 0,641 149 158 36,2
5x70 RM 0,443 191 196 40,6
5x95 RM 0,320 234 234 46,7
5x120 RM 0,253 273 268 50,4
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W