Power cable 0,6/1 kV with Cu conductors, rubber G16 insulated and PVC sheathed

FG16R16

APPLICATION

Reference Guidance CEI 20-67:
Cable suitable for energy supply in industry, building sites and construction industry. For fixed wiring indoors and outdoors, even wet; for direct and indirect underground wiring. Suitable for installation at open air, on walls, metal structures, cable trays, pipes, wiring holders and similar devices. Suitable for bundle installations in environments at risk of fire.

CERTIFICATES


CONSTRUCTION

  • Sheath
    PVC compound R16 quality, gray
  • Conductors
    Cu, class 5 according to EN 60228
  • Insulation
    Rubber compound G16 quality

TEHNICAL CHARACTERISTICS

  • Standard
    CEI 20-13, IEC 60502-1
  • CPR class
    Cca-s3,d2,a3
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Core identification
    Acc. to HD 308 s2
  • Bending radius (min)
    single-core - 6D
  • Max. working temperature
    90°C
  • Min. temp. for cable laying
    -15°C
  • Max. short-circuit temperature
    250°C
Nominal cross-section Max. Resistance at 20°C Outer diam. (approx.) Cable weight (approx.) Current capacity burried pipe, 20°C Current capacity burried pipe, 20°C Current capacity burried, 20°C Current capacity burried, 20°C Current capacity in pipe in air, 30°C Current capacity in air, 30°C Average sheath thickness Average insulation thickness
mm2 Ω/km mm kg/km K=1,5
A
K=1
A
K=1,5
A
K=1
A
A A mm mm
1x1,5 13,3 8,2 55 21 23 24 26 20 24 1,4 0,7
1x2,5 7,98 8,7 66 27 29 31 34 28 33 1,4 0,7
1x4 4,95 9,3 84 35 38 40 43 37 45 1,4 0,7
1x6 3,30 9,9 110 44 48 51 55 48 58 1,4 0,7
1x10 1,91 10,9 150 59 64 68 73 66 80 1,4 0,7
1x16 1,21 11,4 220 77 83 89 96 88 107 1,4 0,7
1x25 0,780 13,2 310 100 108 115 124 117 141 1,4 0,9
1x35 0,554 14,6 410 121 131 139 150 144 176 1,4 0,9
1x50 0,386 16,4 560 150 162 173 186 175 216 1,4 1,0
1x70 0,272 18,3 760 184 199 212 229 222 279 1,4 1,1
1x95 0,206 20,4 960 217 234 250 270 269 342 1,5 1,1
1x120 0,161 22,4 1210 251 271 289 312 312 400 1,5 1,2
1x150 0,129 24,8 1480 287 310 330 356 355 464 1,6 1,4
1x185 0,106 27,2 1790 323 349 371 401 417 533 1,6 1,6
1x240 0,0801 30,4 2320 279 409 436 471 490 634 1,7 1,7
1x300 0,0641 33,0 2840 429 463 493 533 - 736 1,8 1,8
1x400 0,0486 37,7 3735 500 540 575 621 - 868 1,9 2,0
1x500 0,0384 43,6 4660 560 610 650 705 - 998 2,1 2,2
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W