LV (450/750 V) PVC insulated conductor

FR-N07V-AR

APPLICATION

For laying in pipes on top of or under plaster and in closed installation ducts and for internal wiring of machinery, switchgear and distributor systems. The cable is not suitable for direct laying under plaster.

CERTIFICATES


CONSTRUCTION

  • Conductors
    Al conductor, class 2
  • Insulation
    PVC compound

TEHNICAL CHARACTERISTICS

  • Standard
    NF C32-208
  • CPR class
    Eca
  • Test voltage
    2,5 kV
  • Rated voltage
    450/750 V
  • Min. bending radius
    6D
  • Max. operating temperature
    70
  • Max. short-circuit temperature
    160
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
1x16 RM 1,910 - - 7,2
1x25 RM 1,200 87 - 8,4
1x35 RM 0,868 107 - 9,5
1x50 RM 0,641 131 - 11,3
1x70 RM 0,443 166 - 12,6
1x95 RM 0,320 205 - 14,7
1x120 RM 0,253 239 - 16,2
1x150 RM 0,206 273 - 18,1
1x185 RM 0,164 317 - 20,2
1x240 RM 0,125 378 - 22,9
1x300 RM 0,100 437 - 27
1x400 RM 0,0778 513 - 32
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W