FR-N1 X1G1-AR

Power cable 0,6/1 kV with Al conductors, XLPE insulated and HFFR sheathed

FR-N1 X1G1-AR

APPLICATION

Distribution power cable for static application, mostly in ground, but also within facilities, in cable canals, in concrete. Used in electric power plants, transformer stations, industrial plants, metropolitan networks and other electric plants, where the protection of sensitive equipment in the event of fire is necessary.
With its low smoke zero halogen sheathing it is widely used in industries including, data processing centres, and public buildings where protection against fire risk is paramount.

CERTIFICATES


CONSTRUCTION

  • Sheath
    HFFR compound, black or green
  • Conductors
    Al, class 2 according to EN 60228
  • Insulation
    XLPE compound

TEHNICAL CHARACTERISTICS

  • Standard
    NF C32-323; NF C32-070, cat. C1
  • CPR class
    Eca
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Min.bending radius
    12D
  • Core identification
    acc.to HD 308 S2
  • Min.laying temperature
    -5°C
  • Min.operating temperature
    90°C
  • Max.short-circuit temperature
    250°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
1x25 RM 1,200 101 111 10,8
1x35 RM 0,868 126 134 11,9
1x50 RM 0,641 154 160 13,3
1x70 RM 0,443 198 197 14,5
1x95 RM 0,320 241 234 16,4
1x120 RM 0,253 280 266 18,2
1x150 RM 0,206 324 300 19,9
1x185 RM 0,164 371 337 22,2
1x240 RM 0,125 439 388 25,0
1x300 RM 0,100 508 440 27,5
1x400 RM 0,0778 663 515 30,4
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W