Power cables 0,6/1 kV with XLPE insulation and HFFR sheath

FXQ

APPLICATION

 In earth, ducts, on support brackets, in dry and wet conditions etc., where one does not expect mechanical damages and the cables are not exposed to the mechanical tensile strain. In urban networks, industrial plants, electric power plants and other electricity consumers and for connection of control devices in industry, traffic etc.

CERTIFICATES


CONSTRUCTION

  • Sheath
    HFFR compound
  • Bedding
    Extruded elastomere or plastomere compound or plastic tape
  • Conductors
    Cu rope
  • Insulation
    XLPE compound

TEHNICAL CHARACTERISTICS

  • Standard
    SS 424 02 19-5; HD 604 S1
  • CPR class
    Cca - s1,d1,a1
  • Test voltage
    4 kV
  • UV resistant
    YES
  • Rated voltage
    0,6/1 kV
  • Gases corrosivity
    IEC 61034
  • Bending radius (min)
    multi-core - 12D
  • Max. operating temperature
    90°C
  • Min. temp. for cable laying
    -10°C
  • Max. short-circuit temperature
    250°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
3x4 RM 4,610 42 52 11,4
3x6 RM 3,080 53 64 16,0
3x10 RM 1,830 74 86 18,0
3x16 RM 1,150 98 112 20,0
4x4 RM 4,610 42 52 15,0
4x6 RM 3,080 53 64 16,0
4x10 RM 1,830 74 86 18,0
4x16 RM 1,150 98 112 20,0
5x4 RM 4,610 42 52 17,0
5x6 RM 3,080 53 64 18,5
5x10 RM 1,830 74 86 21,0
5x16 RM 1,150 98 112 24,0
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W