H07V-K (P-F)

LV (450/750 V) PVC insulated flexible conductor

H07V-K (P-F)

APPLICATION

For laying in pipes on top of or under plaster and in closed installation ducts and for internal wiring of machinery, switchgear and distributor systems. The cable is not suitable for direct laying under plaster.

CERTIFICATES


CONSTRUCTION

  • Conductors
    Cu conductor, class 5 acc. to EN 60228
  • Insulation
    PVC compound
  • Insulation colour
    Acc. to EN 50525-1: black, blue, brown, gray, orange, pink, red, turquoise, violet, white and green-yellow

TEHNICAL CHARACTERISTICS

  • Standard
    EN 50525-2-31, IEC 60227-3, SRPS N.C3.202
  • CPR class
    Eca
  • Test voltage
    2,5 kV
  • Rated voltage
    450/750 V
  • Bending radius (min)
    6D
  • Max. operating temperature
    +70°C
  • Max. short-circuit temperature
    +160°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
1x0,75 - 26,0 6 - 2,3
1x1,0 - 19,5 10 - 2,4
1x1,5 - 13,3 17,5 - 3,0
1x2,5 - 7,98 24 - 3,6
1x4 - 4,95 32 - 4,2
1x6 - 3,30 41 - 4,7
1x10 - 1,910 57 - 6,1
1x16 - 1,210 76 - 7,2
1x25 - 0,780 101 - 8,4
1x35 - 0,554 125 - 9,5
1x50 - 0,386 151 - 11,3
1x70 - 0,272 192 - 12,6
1x95 - 0,206 232 - 14,7
1x120 - 0,161 269 - 16,2
1x150 - 0,129 300 - 18,1
1x185 - 0,106 341 - 20,2
1x240 - 0,0801 400 - 22,9
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W