LV (450/750 V) PVC insulated conductor

H07V-R

APPLICATION

For laying in pipes on top of or under plaster and in closed installation ducts and for internal wiring of machinery, switchgear and distributor systems. The cable is not suitable for direct laying under plaster.

CERTIFICATES


CONSTRUCTION

  • Conductors
    Cu rope, class 2
  • Insulation
    PVC compound

TEHNICAL CHARACTERISTICS

  • Standard
    EN 50525-2-31, IEC 60227
  • CPR class
    Eca
  • Test voltage
    2,5 V
  • Rated voltage
    450/750 V
  • Core identification
    Acc. to EN 50525-1
  • Bending radius (min)
    6D
  • Max. operating temperature
    +70°C
  • Max. short-circut temperature
    +160°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Outer diam. (approx.) Metal weight Cable weight (approx.) Current capacity in air, 30°C Average insulation thickness
mm2 Ω/km mm kg/km kg/km A mm
1x1,5 RM 12,1 3,0 14,4 23 17,5 0,7
1x2,5 RM 7,41 3,6 24 35 24 0,8
1x4 RM 4,61 4,2 38,4 51 32 0,8
1x6 RM 3,08 4,7 57,6 71 41 0,8
1x10 RM 1,830 6,1 96 120 57 1,0
1x16 RM 1,150 7,2 153,6 180 76 1,0
1x25 RM 0,727 8,4 240 280 101 1,2
1x35 RM 0,524 9,5 336 380 125 1,2
1x50 RM 0,387 11,3 480 490 151 1,4
1x70 RM 0,268 12,6 672 710 192 1,4
1x95 RM 0,193 14,7 912 980 232 1,6
1x120 RM 0,153 16,2 1152 1210 269 1,6
1x150 RM 0,124 18,1 1440 1510 300 1,8
1x185 RM 0,0991 20,2 1776 1900 341 2,0
1x240 RM 0,0754 22,9 2304 2490 400 2,2
1x300 RM 0,0601 27,0 2880 3050 458 2,4
1x400 RM 0,0470 32,0 3840 3900 546 2,6
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W