Power cable 0,6/1 kV with Al conductors, XLPE insulated, with halogen-free sheath

HIK-Al-M

APPLICATION

Halogen-free UV resistant cable for fixed installation in buildings, channels, tubes, in open air and in the ground. The insulation must not be exposed to UV light. Installed acc. to The Danish Heavy Regulations.

CERTIFICATES


CONSTRUCTION

  • Sheath
    Halogen-free compound
  • Bedding
    Extruded elastomere or plastomere compound or plastic tape
  • Conductors
    Al, class 1 according to EN 60228
  • Insulation
    XLPE compound

TEHNICAL CHARACTERISTICS

  • Standard
    HD 603 S1, p.5B, IEC 60502-1
  • CPR class
    Eca
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Fire properties
    EN 60332-1-2
  • Core identification
    Acc. to HD 308 S2
  • Working temperature
    -40°C to 90°C
  • Bending radius (min)
    15D
  • Min. temp. for cable laying
    -0°C to 50°C
  • Max. short-circuit temperature
    250°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Outer diam. (approx.) Metal weight Cable weight (approx.)
mm2 Ω/km A mm kg/km kg/km
4x16 RE 1,910 77 18 185,6 325
4x25 RE 1,200 97 22,1 290 462
4x50 SE 0,641 146 26 580 832
4x95 SE 0,320 227 33,6 1102 1474
4x150 SE 0,206 304 42 1740 2301
4x240 SE 0,125 409 52,1 2784 3632
5G16 RE 1,910 77 20 232 390
5G25 RE 1,200 97 24 362,5 580
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W