Power cable 0,6/1 kV with Al conductors, XLPE insulated, with halogen-free sheath

HIK-AL-S

APPLICATION

Halogen-free UV resistant cable for fixed installation in buildings, channels, tubes, in open air and in the ground. The insulation must not be exposed to UV light. Installed acc. to The Danish Heavy Regulations.

CERTIFICATES


CONSTRUCTION

  • Sheath
    Halogen-free compound
  • Bedding
    Extruded elastomere or plastomere compound or plastic tape
  • Conductors
    Al, class 2 according to EN 60228
  • Insulation
    XLPE compound

TEHNICAL CHARACTERISTICS

  • Standard
    HD 603 S1, p.5B, IEC 60502-1
  • CPR class
    Eca
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Fire properties
    EN 60332-1-2
  • Core identification
    Acc. to HD 308 S2
  • Working temperature
    -40°C to 90°C
  • Bending radius (min)
    15D
  • Min. temp. for cable laying
    -0°C to 50°C
  • Max. short-circuit temperature
    250°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Outer diam. (approx.) Metal weight Cable weight (approx.)
mm2 Ω/km A mm kg/km kg/km
1x95 RM 0,320 252 17,1 275,5 448
4x50 SM 0,641 146 27,7 580 900
4X70 SM 0,443 187 31 812 1180
4x95 SM 0,320 227 35,1 1102 1450
4x120 SM 0,253 263 42 1392 1945
4x150 SM 0,206 304 43,6 1740 2210
4x185 SM 0,164 347 48 2146 2925
4x240 SM 0,125 409 23,7 2784 3485
4x300 SM 0,100 471 59 3480 4575
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W