Halogen-free installation cables 300/500 V

HMH

APPLICATION

Where halogen-free and environmentally friendly cables are required. For fixed installation in dry and wet rooms and outside as well as in the open air. Can be laid in the ground. May be bricked in and embedded directly. Not suitable for embedment in vibrated concrete. Conductor insulation must be protected against light exposure. Installation to be performed by a licensed electrician only.

CERTIFICATES


CONSTRUCTION

  • Sheath
    HFFR compound
  • Bedding
    Extruded halogen-free polymer
  • Conductors
    Cu, class1 or 2 according to EN 60228
  • Insulation
    XLPE halogen – free compound

TEHNICAL CHARACTERISTICS

  • Standard
    DIN VDE 0250-215
  • CPR class:
    Eca
  • Test voltage
    2000 V
  • Rated voltage
    300/500 V
  • Core identification
    acc. to HD 308 S2
  • Min. bending radius
    10D
  • Min. laying temperature
    -15°C
  • Max. working temperature
    90°C
  • Max. short-circuit temperature
    250°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
1x4 RE 4,61 42 36 6,3
1x6 RE 3,08 54 44 6,8
1x10 RE 1,830 75 58 7,7
1x16 RE 1,150 100 75 8,7
2x1,5 RE 12,1 23 21 8,2
2x2,5 RE 7,41 32 28 9,0
2x4 RE 4,61 42 36 10,0
2x6 RE 3,08 54 44 11,4
3x1,5 RE 12,1 23 21 8,7
3x2,5 RE 7,41 32 28 9,5
3x4 RE 4,61 42 36 10,6
3x6 RE 3,08 54 44 12,1
4x1,5 RE 12,1 23 21 9,4
4x2,5 RE 7,41 32 28 10,3
4x4 RE 4,61 42 36 12,0
4x6 RE 3,08 54 44 13,2
4x10 RE 1,830 75 58 15,1
4x16 RE 1,150 100 75 17,7
5x1,5 RE 12,1 23 21 10,2
5x2,5 RE 7,41 32 28 11,2
5x4 RE 4,61 42 36 13,0
5x6 RE 3,08 54 44 14,3
5x10 RE 1,830 75 58 16,5
5x16 RE 1,150 100 75 19,3
7x1,5 RE 12,1 23 21 11,8
7x2,5 RE 7,41 32 28 13,4
12x1,5 RE 12,1 23 21 15,0
12x2,5 RE 7,41 32 28 17,1
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W