LV (0,6/1 kV) power cables with PVC insulation and PVC sheath, with concentric conductor

MCMK

APPLICATION

Distribution and signalling power cable for static outdoor application (with protection against direct UV-irradiation), in ground, in water, within facilities, in cable canals, in concrete, in conditions requiring increased electric protection and protection against mechanical damages. Used in electric power plants, transformer stations, industrial plants, metropolitan networks and other electric plants and for connection of signalling devices in industry, traffic and similar. Concentric conductor can be used as neutral, protective or earth connection, and if there is a danger of damages caused by digging, it acts as protection against contact voltage in case of rough insulation damage.

CERTIFICATES


CONSTRUCTION

  • Sheath
    PVC compound
  • Bedding
    Extruded elastomere or plastomere compound or plastic tape
  • Conductors
    Cu conductor, class 1 or 2, according to EN 60228
  • Insulation
    PVC compound
  • Concentric conductor
    Cu wires with counter helix of Cu tape

TEHNICAL CHARACTERISTICS

  • Standard
    HD 603 S1, SFS 4880, SS 424 14 18
  • CPR class
    Eca
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Core identification
    According to HD 308 S2
  • Bending radius (min)
    12xD
  • Min. laying temperature
    -5°C
  • Max. operating temperature
    +70°C
  • Max. short-circuit temperature
    +160°C
Nominal cross-section Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.) Metal weight Cable weight (approx.)
mm2 Ω/km A A mm kg/km kg/km
2x6/6 3,08 43 57 15,4 98,2 333
2x10/10 1,830 60 77 17,6 163 466
3x6/6 3,08 43 57 15,9 158,8 416
3x10/10 1,830 60 77 19 263,8 600
3x16/16 1,150 80 100 21 421,7 848
3x25/16 0,727 102 130 24,5 675 1181
3x35/16 0,524 126 160 27 941 1498
3x50/25 0,387 153 190 28 1288,3 2039
3x70/35 195 240 31 1862,2 2765
3x95/50 0,193 236 285 37 2569,9 3761
3x120/70 0,153 274 325 39 3270,5 4736
3x150/70 0,124 317 370 43 4028,7 5663
3x185/95 0,0991 361 420 47,1 4979,9 7043
3x240/120 0,0754 427 480 52,8 6531 9110
3x300/150 0,0601 492 550 63 9240 11500
4x6/6 3,08 43 57 17,5 211,9 507
4x10/10 1,830 60 77 20,7 352 740
4x16/16 1,150 80 100 23 562 1040
4x25/16 0,727 102 130 26 901 1450
4x35/16 0,524 126 160 28 1257,1 1850
4x50/25 0,387 153 190 32 1717,7 2580
4x70/35 0,268 195 240 35 2482,9 3523
4x95/50 0,193 236 285 41 3426,5 4799
4x120/70 0,153 274 325 44 4360,6 6032
4x150/70 0,124 317 370 49 5371,7 7265
4x185/95 0,0991 361 420 54 6639,8 9018
4x240/120 0,0754 427 480 60 8708,4 11673
4x300/150 0,0601 492 550 66 11900 14500
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W