MMJ/PFXP/EKK Light

Instalation (300/500 V) cables with PVC insulation and PVC sheath

MMJ/PFXP/EKK Light

APPLICATION

For fixed surface and flush-mounted installations, indoors and outdoors. Also suitable for installation in a slot covered with plaster as specified e.g. in SFS 6000.
Not suitable for installation directly in ground nor directly in concrete without protective ducting. Not for installations subject to electrical interference.
Direct sunlight (UV) may slightly alter the colour of the sheath.

CERTIFICATES


CONSTRUCTION

  • Sheath
    PVC compound
  • Bedding
    Extruded PVC compound
  • Conductors
    Cu conductors, class 1 according to EN 60228
  • Insulation
    PVC compound

TEHNICAL CHARACTERISTICS

  • Standard
    SFS 2091, SS 424 02 19-3
  • CPR class
    Eca
  • Rated voltage
    300/500 V
  • Testing voltage
    2 kV
  • Core identification
    According to HD 308 S2
  • Operating temperature
    -15°C up to 70°C
  • Min. laying temperature
    -15°C
  • Max. conductor temperature
    70°C
  • Max. short-circuit temperature
    160°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Outer diam. (approx.) Metal weight Cable weight (approx.)
mm2 Ω/km A mm kg/km kg/km
3G1,5 RE 12,1 18 9 43,2 125
3G2,5 RE 7,41 26 10 72 180
3G4 RE 4,61 34 12 115,2 280
4G1,5 RE 12,1 18 10 57,6 155
4G2,5 RE 7,41 26 11 96 220
4G4 RE 4,61 34 13 153,6 340
5G1,5 RE 12,1 18 11 72 180
5G2,5 RE 7,41 26 13 120 260
5G4 RE 4,61 34 14 192 410
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W