N2XBY

Power cable 0,6/1 kV with Cu conductors, XLPE insulated and PVC sheathed

N2XBY

APPLICATION

Distribution power cable for static application, mostly in ground, but also in water, within facilities, in cable canals, in concrete. Used in electric power plants, transformer stations, industrial plants, metropolitan networks and other electric plants. Applied in conditions requiring protection against heavier mechanical damages, but where cables are not exposed to heavier tensile strain.

CERTIFICATES


CONSTRUCTION

  • Sheath
    PVC compound DMV 6
  • Armour
    Two galvanized steel tapes
  • Bedding
    Extruded elastomere or plastomere compound or plastic tape
  • Conductors
    Cu, class 1 or 2 according to EN 60228
  • Insulation
    XLPE compound DIX 3

TEHNICAL CHARACTERISTICS

  • Standard
    HD 603 S1, IEC 60502-1
  • CPR class
    Eca
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Core identification
    Acc. to HD 308 S2
  • Min.bending radius
    single-core - 15D; multicore - 12D
  • Min.laying temperature
    -5°C
  • Max.operating temperature
    90°C
  • Max.short-circuit temperature
    250°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
2x4 RE/RM 4,61 42 52 14,2
2x6 RE/RM 3,08 53 64 15,2
2x10 RE/RM 1,83 74 86 17,2
2x16 RE/RM 1,15 98 112 19,0
2x25 RM 0,727 133 145 22,0
2x35 RM 0,524 162 174 24,2
2x50 RM 0,387 197 206 27,4
2x70 RM 0,268 250 254 31,4
3x1,5 RE/RM 12,1 24 31 14,5
3x2,5 RE/RM 7,41 32 40 15,3
3x4 RE/RM 4,610 42 52 16,2
3x6 RE/RM 3,080 53 64 17,3
3x10 RE/RM 1,830 74 86 18,9
3x16 RE/RM 1,150 98 112 20,9
3x25 RE/RM 0,727 133 145 23,2
3x35 SM 0,524 162 174 25,6
3x50 SM 0,387 197 206 30,2
3x70 SM 0,268 250 254 34,5
3x95 SM 0,193 308 305 38,3
3x120 SM 0,153 359 348 42,0
3x150 SM 0,124 412 392 46,3
3x185 SM 0,0991 475 444 50,6
3x240 SM 0,0754 564 517 56,7
4x1,5 RE/RM 12,1 24 31 15,2
4x2,5 RE/RM 7,41 32 40 16,1
4x4 RE/RM 4,610 42 52 17,2
4x6 RE/RM 3,080 53 64 18,4
4x10 RE/RM 1,830 74 86 19,3
4x16 RE/RM 1,150 98 112 21,5
4x25 RE/RM 0,727 133 145 25,1
4x35 SM 0,524 162 174 27,8
4x50 SM 0,387 197 206 32,8
4x70 SM 0,268 250 254 37,5
4x95 SM 0,193 308 305 41,7
4x120 SM 0,153 359 348 45,8
4x150 SM 0,124 412 392 51,4
4x185 SM 0,0991 475 444 56,2
4x240 SM 0,0754 564 517 62,6
5x1,5 RE/RM 12,1 24 31 16,0
5x2,5 RE/RM 7,41 32 40 17,0
5x4 RE/RM 4,610 42 52 18,2
5x6 RE/RM 3,080 53 64 19,5
5x10 RE/RM 1,830 74 86 20,7
5x16 RE/RM 1,150 98 112 23,1
5x25 RM 0,727 133 145 72,2
5x35 RM 0,524 162 174 30,2
5x50 RM 0,387 197 206 35,6
5x70 RM 0,268 250 254 40,7
5x95 RM 0,193 308 305 45,4
7x1,5 RE/RM 12,1 24 31 15,19
10x1,5 RE/RM 12,1 24 31 18,02
12x1,5 RE/RM 12,1 24 31 18,46
16x1,5 RE/RM 12,1 24 31 20
19x1,5 RE/RM 12,1 24 31 20,85
21x1,5 RE/RM 12,1 24 31 21,71
27x1,5 RE/RM 12,1 24 31 24,5
37x1,5 RE/RM 12,1 24 31 26,91
7x2,5 RE/RM 7,41 32 40 16,33
10x2,5 RE/RM 7,41 32 40 19,54
12x2,5 RE/RM 7,41 32 40 20,04
16x2,5 RE/RM 7,41 32 40 21,79
19x2,5 RE/RM 7,41 32 40 23,15
21x2,5 RE/RM 7,41 32 40 24,13
27x2,5 RE/RM 7,41 32 40 26,84
37x2,5 RE/RM 7,41 32 40 29,57
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W