Power cable 0,6/1 kV with Al conductors, XLPE insulated and PVC sheathed

NA2XY

APPLICATION

In earth, ducts, on support brackets, in dry and wet conditions etc., where one does not expect mechanical damages and the cables are not exposed to the mechanical tensile strain. In urban networks, industrial plants, electric power plants and other electricity consumers and for connection of control devices in industry, traffic etc.

CERTIFICATES


CONSTRUCTION

  • Sheath
    XLPE compound DMV 6
  • Bedding
    Extruded elastomere or plastomere compound or plastic tape
  • Conductors
    Al, class 1 (RE/SE) or class 2 (RM/SM) according to EN 60228
  • Insulation
    XLPE compound DIX 3

TEHNICAL CHARACTERISTICS

  • Standard
    VDE 0276-603, HD 603 S1
  • CPR class
    Eca
  • Test voltage
    4 Kv
  • Rated voltage
    0,6/1 kV
  • Core identification
    According to HD 308 S2
  • Bending radius (min)
    single-core - 15D; multicore - 12D
  • Min. laying temperature
    -5°C
  • Max. conductor temperature
    90°C
  • Max. short-circuit temperature
    250°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.) Metal weight Cable weight (approx.)
mm2 Ω/km A A mm kg/km kg/km
1x16 RM 1,910 - - 9,5 46,4 122
1x25 RM 1,200 106 114 11,9 72,5 175
1x35 RM 0,868 130 136 13 101,5 206
1x50 RM 0,641 161 162 14,9 145 267
1x70 RM 0,443 204 199 17 203 358
1x95 RM 0,320 252 238 18,9 275,5 451
1x120 RM 0,253 295 272 20,7 348 546
1x150 RM 0,206 339 305 22,7 435 655
1x185 RM 0,164 395 347 25,1 536,5 800
1x240 RM 0,125 472 404 27,6 696 987
1x300 RM 0,100 547 457 31,9 870 1324
1x400 RM 0,0778 643 525 34,9 1160 1640
1x500 RM 0,0605 754 601 39,3 1450 2030
1x630 RM 0,0469 882 687 44,1 1827 2400
1x800 RM 0,0367 1019 776 46,5 2320 2505
1x1000 RM 0,0291 1157 865 52 2900 3115
3x16 RM 1,910 - - 16,5 139,2 397
3x25 RM 1,200 102 112 20 217,5 587
3x35 RM/SM 0,868 126 135 22,5 304,5 531
3x50 RM 0,641 149 158 57,6 435 1007
3x70 RM 0,443 191 196 30,6 609 1401
3x95 RM 0,320 234 234 33,8 826,5 1801
3x120 RM 0,253 273 268 37,5 1044 2226
3x50 SE/SM 0,641 149 158 26 435 720
3x70 SE/SM 0,443 191 196 29,7 609 963
3x95 SE/SM 0,320 234 234 33,4 826,5 1246
3x120 SE/SM 0,253 273 268 37,1 1044 1545
3x150 SE/SM 0,206 311 300 41,2 1305 1916
3x185 SE/SM 0,164 360 342 45,7 1609,5 2347
3x240 SE/SM 0,125 427 398 51,6 2088 2987
3x300 SE/SM 0,100 507 457 56,7 2610 3663
3x70+35 SM/SM 0,443/0,868 191 196 28,8 655,4 935
3x95+50 SM/SM 0,320/0,641 234 234 32,2 899 1120
3x120+70 SM/SM 0,253-0,443 273 268 34,6 1145,5 1430
3x150+70 SM/SM 0,206/0,443 311 300 38,5 1450 1950
3x185+95 SM/SM 0,164/0,320 360 342 42,4 1812,5 2345
3x240+120 SM/SM 0,125/0,253 427 398 47,2 2363,5 2980
4x16 RE/RM 1,910 - - 22,1 185,6 596
4x25 RE/RM 1,200 102 112 26,2 290 851
4x35 RE/RM 0,868 126 135 28,9 406 1055
4x35 SM 0,868 126 135 25,9 406 690
4x50 SE/SM 0,641 149 158 28,4 580 832
4x70 SE/SM 0,443 191 196 32,4 812 1234
4x95 SE/SM 0,320 234 234 35,6 1102 1460
4x120 SE/SM 0,253 273 268 40,6 1392 1861
4x150 SE/SM 0,206 311 300 44,8 1740 2386
4x185 SE/SM 0,164 360 342 49,2 2146 2866
4x240 SE/SM 0,125 427 398 54,9 2784 3616
4x300 SE/SM 0,100 507 457 58,8 3480 4500
4x16+1,5 RE/RM 1,910 - - 22,1 185,6 615
4x25+1,5 RE/RM 1,200 102 112 26,2 290 870
4x35+1,5 RE/RM 0,868 126 165 28,9 406 1074
4x35+1,5 SM 0,868 126 135 23,1 406 630
4x50+1,5 SE/SM 0,641 149 158 26 580 847
4x70+1,5 SE/SM 0,443 191 196 30 812 1135
4x95+1,5 SE/SM 0,320 234 234 33,6 1102 1480
4x120+1,5 SE/SM 0,253 273 268 37,3 1392 1826
4x150+1,5 SE/SM 0,206 311 300 42 1740 2282
4x185+1,5 SE/SM 0,164 360 342 46,3 2146 2766
4x240+1,5 SE/SM 0,125 427 398 52,1 2784 3572
4x300+1,5 SE/SM 0,100 507 457 56,8 3480 4374
5x16 RM 1,910 - - 23,4 232 625
5x25 RM 1,200 102 112 28,2 362,5 950
5x35 RM 0,868 126 135 31 507,5 1195
5x50 RM 0,641 149 158 36,8 725 1540
5x70 RM 0,443 191 196 42,8 1015 2240
5x95 RM 0,320 234 234 48,5 1377,5 3015
5x120 RM 0,253 273 268 53,6 1740 3580
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W