(N)HXH (FRHF) FE180/E30-E60

Halogen-free installation cable 300/500 V, with improved properties under fire, and 30-60-minute circuit integrity maintenance

(N)HXH (FRHF) FE180/E30-E60

APPLICATION

These cables are suitable for fixed installation in dry and damp environment, on or under plaster, on cable trays, same as in walls and concrete. Not intended for direct laying in ground or water. For outdoor application can be laid in tubes, but in that case should be taken all precautionary measures necessary to prevent water penetration into the tubes. Suitable for electric installations with marked fire-fighting and function preserving requirements, for alarm systems, fire sensors, evacuation elevators and other supply systems in an emergency. Appropriate for application in all situations where people and material goods need to be protected in case of fire. Recommended for public buildings frequented by a lot of people, and for buildings of high material value, for industrial complexes, electric power plants, transformer stations, municipal facilities, hotels, shopping malls, hospitals, schools, airports, underground railways and similar. Important - these cables should not be laid on common trays, but on fire-resistant trays which retain their geometry in case of fire. Keeping these cables in the same position in case of fire, enables additional protection of cable conductivity, by means of the mineral layer discharged around the cable at increased temperature.

CONSTRUCTION

  • Sheath
    LSZH compound, orange
  • Bedding
    Extruded elastomere or plastomere LSZH compound
  • Conductors
    Cu conducrtors, class 1 or 2 according to EN 60228
  • Insulation
    Ceramizable (silicone) compound

TEHNICAL CHARACTERISTICS

  • Standard
    According to DIN VDE 0266, HD 604 S1
  • Halogen free
    IEC 60754
  • Test voltage
    2 kV
  • Rated voltage
    300/500 V
  • Fire retardant
    IEC 60332-3-24, Cat. C
  • Flame retardant
    IEC 60332-1-2
  • Low smoke emission
    IEC 61034
  • Bending radius (min)
    12xD
  • Min. laying temperature
    -5°C
  • Circuit integrity, FE180
    IEC 60331-21, IEC 60331-11
  • Circuit integrity, E30-E60
    VDE 4102-12
  • Max. conductor temperature
    90°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Outer diam. (approx.) Metal weight Cable weight (approx.)
mm2 Ω/km A mm kg/km kg/km
1x10 RE 1,830 77 8 96 154
1x16 RE/RM 1,150 102 9,1 153,6 225
1x25 RM 0,727 138 11 240 342
2x1,5 RE 12,1 26 8,8 28,8 125
2x2,5 RE 7,41 34 9,6 48 160
2x4 RE 4,61 44 10,6 76,8 211
2x6 RE 3,08 56 11,6 115,2 272
2x10 RE/RM 1,830 74 13,6 192 403
2x16 RE/RM 1,150 98 15,4 307,2 568
2x25 RM 0,727 133 18,8 480 863
3x1,5 RE 12,1 24 9,7 432 155
3x2,5 RE 7,41 32 10,5 72 202
3x4 RE 4,61 42 11,6 115,2 268
3x6 RE 3,08 53 13,1 172,8 363
3x10 RE/RM 1,830 74 15,2 288 536
3x16 RE/RM 1,150 98 17,1 460,8 761
4x1,5 RE 12,1 24 10,0 57,6 170
4x2,5 RE 7,41 32 10,9 96 227
4x4 RE 4,61 42 12,6 153,6 321
4x6 RE 3,08 53 14,2 230,4 438
4x10 RE/RM 1,830 74 16,7 384 667
4x16 RE/RM 1,150 98 19,1 614,4 964
4x25 RM 0,727 133 23,1 960 1456
5x1,5 RE 12,1 24 10,8 72 197
5x2,5 RE 7,41 32 11,8 120 266
5x4 RE 4,61 42 13,6 192 378
5x6 RE 3,08 53 15,3 288 518
5x10 RE/RM 1,830 74 18,1 480 791
5x16 RE/RM 1,150 98 21,1 768 1180
5x25 RM 0,727 133 25,6 1200 1786
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W