Power cable 0,6/1 kV with Cu conductors, PVC insulated and sheathed

NYBY

APPLICATION

Distribution and signal power cable for static application, mostly in ground, but also within and outside facilities, in cable canals, in concrete. Used in electric power plants and other electric plants, in industry, metropolitan networks and for connection of signalling devices in industry, traffic and similar. Resistant to mechanical loads, able to sustain heavier mechanical tensile strains, could be laid slantingly or vertically, same as on grounds exposed to land-sliding.

CERTIFICATES


CONSTRUCTION

  • Armour
    Two galvanized steel tapes
  • Sheath
    PVC compound DMV 5
  • Bedding
    Extruded elastomere or plastomere compound or plastic tape
  • Conductors
    Cu, class 1 or 2 according to EN 60228
  • Insulation
    PVC compound DIV 4

TEHNICAL CHARACTERISTICS

  • Standard
    HD 603 S1, IEC 60502-1
  • CPR class
    Fca
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Core identification
    According to HD 308 S2
  • Bending radius (min)
    12xD
  • Min. laying temperature
    -5°C
  • Max. conductor temperature
    70°C
  • Max. short-circuit temperature
    160°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.) Metal weight Cable weight (approx.)
mm2 Ω/km A A mm kg/km kg/km
2x4 RE 4,61 34 47 15,4 76,8 432
2x6 RE 3,08 43 59 16,4 115,2 505
2x10 RE/RM 1,830 59 79 18,4 192 657
2x16 RM 1,150 79 102 20,2 307,2 859
2x25 RM 0,727 106 133 23,2 480 1187
2x35 RM 0,524 129 159 25,4 672 1482
2x50 RM 0,387 157 188 29 960 2002
3x1,5 RE 12,1 19,5 27 14,9 43,2 357
3x2,5 RE 7,41 25 36 15,7 72 414
3x4 RE/RM 4,61 34 47 17,7 115,2 530
3x6 RE/RM 3,08 43 59 18,8 172,8 627
3x10 RE/RM 1,830 59 79 19,3 288 793
3x16 RM 1,150 79 102 21,2 460,8 1059
3x25 RM 0,727 106 133 24,5 720 1490
3x35 SM 0,524 129 159 26,9 1008 1891
3x50 SM 0,387 157 188 31,9 1440 2777
3x70 SM 0,268 199 232 35,8 2016 3589
3x95 SM 0,193 246 280 40,5 2736 4647
3x120 SM 0,153 285 318 43,7 3456 5673
3x25+16 RM/RE 0,727/1,150 106 133 26,5 873,6 1587
3x35+16 RM/RE 0,524/1,150 129 159 28,7 1161,6 1985
3x50+25 SM/RM 0,387/0,727 157 188 33,8 1680 2953
3x70+35 SM/SM 0,268/0,524 199 232 36 2352 3433
3x95+50 SM/SM 0,193/0,387 246 280 41,2 3216 4588
3x120+70 SM/SM 0,153/0,268 285 318 45 4128 5640
3x150+70 SM/SM 0,124/0,268 326 359 48,6 4992 6685
3x185+95 SM/SM 0,0991/0,193 374 406 53,8 6240 8205
3x240+120 SM/SM 0,0754/0,153 445 473 56 8064 10364
3x300+150 SM/SM 0,0601/0,124 511 535 66,5 10080 12769
4x1,5 RE 12,1 19,5 27 15,7 57,6 394
4x2,5 RE 7,41 25 36 16,6 96 463
4x4 RE/RM 4,61 34 47 18,8 153,6 603
4x6 RE/RM 3,08 43 59 20 230 724
4x10 RE/RM 1,830 59 79 20,8 384 939
4x16 RM 1,150 79 102 22,9 614,4 1272
4x25 RM 0,727 106 133 26,6 960 1810
4x35 SM 0,524 129 159 29,2 1344 2319
4x50 SM 0,387 157 188 34,7 1920 3376
4x70 SM 0,268 199 232 38,9 2688 4402
4x95 SM 0,193 246 280 44,2 3648 5818
4x120 SM 0,153 285 318 47,8 4608 7027
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W