LV (300/500 V) PVC insulated and sheathed installation cable

NYM

APPLICATION

Installation cable suitable for household and industrial usage. Laid on or under plaster, in walls or concrete, without special mechanical protection, but not in dry or pre-stressed concrete. Suitable for dry, same as damp or wet environment; for internal or external application (only if the cable is protected against direct sunlight.

CONSTRUCTION

  • Sheath
    PVC compound TM1
  • Bedding
    PVC or EPDM compound
  • Conductors
    Cu conductor, class 1 or 2 acc. to EN 60228
  • Insulation
    PVC compound TI1

TEHNICAL CHARACTERISTICS

  • Standard
    DIN VDE 0250-204
  • CPR class
    Fca
  • Test voltage
    2 kV
  • Rated voltage
    300/500 V
  • Core identification
    Acc. to HD 308 S2
  • Bending radius (min)
    6D
  • Max. operating temperature
    +70°C
  • Max. short-circuit temperature
    +160°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
1x1,5 RE 12,1 17,5 - 5,3
1x2,5 RE 7,40 24 - 5,8
1x4 RE 4,60 32 - 6,5
1x6 RE 3,08 41 - 7,1
1x10 RE 1,830 57 - 8,2
1x16 RM 1,150 76 - 9,3
2x1,5 RE 12,1 17,5 - 8,2
2x2,5 RE 7,40 24 - 9,5
2x4 RE 4,61 32 - 11,2
2x6 RE 3,08 41 - 12,3
1x10 RE 1,830 57 - 15
2x16 RM 1,150 76 - 17,1
2x25 RM 0,727 101 - 20,5
2x35 RM 0,524 125 - 22,6
3x1,5 RE 12,1 17,5 - 8,5
3x2,5 RE 7,40 24 - 10
3x4 RE 4,61 32 - 11,8
3x6 RE 3,08 41 - 13
3x10 RE 1,830 57 - 15,9
3x16 RM 1,150 76 - 18,1
3x25 RM 0,727 101 - 22,2
3x35 RM 0,524 125 - 24,5
4x1,5 RE 12,1 17,5 - 9,8
4x2,5 RE 7,40 24 - 11,1
4x4 RE 4,61 32 - 13,7
4x6 RE 3,08 41 - 14,7
4x10 RE 1,830 57 - 17,4
4x16 RM 1,150 76 - 19,8
4x25 RM 0,727 101 - 24,3
4x35 RM 0,524 125 - 26,9
5x1,5 RE 12,1 17,5 - 10,6
5x2,5 RE 7,40 24 - 12
5x4 RE 4,61 32 - 14,2
5x6 RE 3,08 41 - 15,7
5x10 RE 1,830 57 - 18,8
5x16 RM 1,150 76 - 22,1
5x25 RM 0,727 101 - 26,7
5x35 RM 0,524 125 - 30,4
7x1,5 RE 12,1 17,5 - 12,5
7x2,5 RE 7,40 24 - 12,8
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W