Power cable 0,6/1 kV with Cu conductors, PVC insulated and sheathed

NYRY

APPLICATION

Distribution and signal power cable for static application, mostly in ground, but also within and outside facilities, in cable canals, in concrete. Used in electric power plants and other electric plants, in industry, metropolitan networks and for connection of signalling devices in industry, traffic and similar. Resistant to mechanical loads, able to sustain heavier mechanical tensile strains, could be laid slantingly or vertically, same as on grounds exposed to land-sliding.

CONSTRUCTION

  • Armour
    A layer of round galvanized steel wires
  • Sheath
    PVC compound DMV 5
  • Bedding
    Extruded elastomere or plastomere compound or plastic tape
  • Conductors
    Cu, class 2 according to EN 60228
  • Insulation
    PVC compound DIV 4

TEHNICAL CHARACTERISTICS

  • Standard
    HD 603 S1, IEC 60502-1
  • CPR class
  • Test voltage
    3,5 kV
  • Rated voltage
    0,6/1 kV
  • Core identification
    Acc.to HD 308 S2
  • Min.bending radius
    single-core - 15D; multicore - 12D
  • Min.laying temperature
    -5°C
  • Max.operating temperature
    70°C
  • Max.short-circuit temperature
    160°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
3x1,5 RM 12,1 19,5 27 12,7
3x2,5 RM 7,41 25 36 13,5
3x4 RM 4,61 34 47 15,5
3x6 RM 3,08 43 59 16,6
3x10 RM 1,830 59 79 19,0
3x16 RM 1,150 779 102 20,9
3x25 RM 0,727 106 133 24,9
3x35 RM 0,524 129 159 27,3
3x50 RM 0,387 157 188 31,1
3x70 RM 0,268 199 232 35,4
3x95 RM 0,193 246 280 40,1
3x120 RM 0,153 285 318 44,3
3x35 SM 0,524 129 159 29,5
3x50 SM 0,387 157 188 33,6
3x70 SM 0,268 199 232 36,9
3x95 SM 0,193 246 280 42,6
3x120 SM 0,153 285 318 46,0
3x150 SM 0,124 329 357 51,3
3x185 SM 0,0991 377 402 55,9
3x240 SM 0,0754 443 463 62,6
4x1,5 RM 12,1 19,5 27 13,5
4x2,5 RM 7,41 25 36 14,4
4x4 RM 4,61 34 47 17,3
4x6 RM 3,08 43 59 18,5
4x10 RM 1,830 59 79 20,5
4x16 RM 1,150 779 102 23,3
4x25 RM 0,727 106 133 27,0
4x35 RM 0,524 129 159 29,6
4x50 RM 0,387 157 188 34,7
4x70 RM 0,268 199 232 38,5
4x95 RM 0,193 246 280 44,8
4x120 RM 0,153 285 318 48,4
4x35 SM 0,524 129 159 32,1
4x50 SM 0,387 157 188 36,7
4x70 SM 0,268 199 232 41,3
4x95 SM 0,193 246 280 46,7
4x120 SM 0,153 285 318 51,5
4x150 SM 0,124 329 357 56,4
4x185 SM 0,0991 377 402 61,5
4x240 SM 0,0754 443 463 69,0
5x1,5 RM 12,1 19,5 27 14,3
5x2,5 RM 7,41 25 36 15,4
5x4 RM 4,61 34 47 17,8
5x6 RM 3,08 43 59 19,9
5x10 RM 1,830 59 79 22,0
5x16 RM 1,150 779 102 25,2
5x25 RM 0,727 106 133 29,2
5x35 RM 0,524 129 159 32,2
5x50 RM 0,387 157 188 37,8
5x70 RM 0,268 199 232 41,9
5x95 RM 0,193 246 280 48,7
5x120 RM 0,153 285 318 53,1
5x35 SM 0,524 129 159 34,9
5x50 SM 0,387 157 188 40,1
5x70 SM 0,268 199 232 45,1
5x95 SM 0,193 246 280 51,1
5x120 SM 0,153 285 318 56,4
5x150 SM 0,124 329 357 61,8
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W