Power cable 0,6/1 kV with Cu conductors, PVC insulated and sheathed

NYY

APPLICATION

In earth, ducts, on support brackets, in dry and wet conditions etc., where one does not expect mechanical damages and the cables are not exposed to the mechanical tensile strain. In urban networks, industrial plants, electric power plants and other electricity consumers and for connection of control devices in industry, traffic etc.

CERTIFICATES


CONSTRUCTION

  • Sheath
    PVC compound DMV 5
  • Bedding
    Extruded elastomere or plastomere compound or plastic tape
  • Conductors
    Cu, class 1 or 2 according to EN 60228
  • Insulation
    PVC compound DIV 4

TEHNICAL CHARACTERISTICS

  • Standard
    VDE 0276-603, HD 603 S1, IEC 60502-1, SRPS N.C5.220
  • CPR class
    Eca
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Core identification
    acc. to HD 308 S2
  • Min. bending radius
    single-core - 15D; multicore - 12D
  • Min. laying temperature
    -5°C
  • Max. operating temperature
    70°C
  • Max. Short-circuit temperature
    160°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
1x4 RE 4,610 37 50 7,9
1X6 RE 3,080 47 62 8,4
1x10 RE 1,830 64 83 9,1
1x10 RM 1,830 64 83 9,7
1x16 RM 1,150 84 107 10,7
1x25 RM 0,727 114 138 12,5
1x35 RM 0,524 139 164 13,6
1x50 RM 0,387 169 195 15,4
1x70 RM 0,268 213 238 17,2
1x95 RM 0,193 264 286 19,5
1x120 RM 0,153 307 286 21,1
1x150 RM 0,124 352 365 23,0
1x185 RM 0,0991 406 413 35,7
1x240 RM 0,0754 483 479 28,7
1x300 RM 0,0601 557 541 31,5
1x400 RM 0,0440 646 614 34,5
3x1,5 RE 12,1 18 - 10,1
3x2,5 RE 7,41 26 - 11,2
3x4 RE 4,610 34 46 14,8
3x6 RE 3,080 43 58 15,9
3x10 RE 1,830 59 78 17,6
3x10 RM 1,830 59 78 18,7
3x16 RM 1,150 78 101 21,0
3x25 RM 0,727 105 132 25,1
3x35 RM 0,524 129 159 27,5
3x50 SM 0,387 157 188 29,5
3x70 SM 0,268 199 232 32,9
3x95 SM 0,193 246 280 37,7
3x120 SM 0,153 285 318 41,3
3x150 SM 0,124 326 359 45,4
3x16+10 RM/RM 1,150/1,830 77 88 21,3
3x25+10 RM/RM 0,727/1,830 98 120 25,5
3x25+16 RM/RM 0,727/1,150 105 132 25,5
3x35+16 RM/RM 0,524/1,150 129 159 28,3
3x35+25 RM/RM 0,524/0,727 134 162 28,3
3x50+25 SM/RM 0,387/0,727 157 188 30,1
3x70+35 SM/RM 0,268/0,524 199 232 33,6
3x70+50 SM/RM 0,268/0,387 199 242 33,6
3x95+50 SM/RM 0,193/0,387 246 280 38,7
3x120+70 SM/RM 0,153/0,268 285 318 41,9
3x150+70 SM/RM 0,124/0,268 326 359 46,2
3x185+95 SM/RM 0,0991/0,193 374 406 50,9
3x240+120 SM/RM 0,0754/0,153 445 473 56,1
3x50+35 SM/SM 0,387/0,524 157 188 29,5
3x70+35 SM/SM 0,268/0,524 199 232 33,3
3x95+50 SM/SM 0,193/0,387 246 280 37,6
3x120+70 SM/SM 0,153/0,268 285 318 403,0
3x150+70 SM/SM 0,124/0,268 326 359 44,7
3x185+95 SM/SM 0,0991/0,193 374 406 50,2
3x240+120 SM/SM 0,0754/0,153 445 473 55,5
4x1,5 RE 12,1 18 - 8,5
4x2,5 RE 7,41 26 - 9,5
4x4 RE 4,610 34 46 15,8
4x6 RE 3,080 43 58 16,9
4x10 RE 1,830 59 78 19,1
4x10 RM 1,830 59 78 19,5
4x16 RM/RE 1,150 78 107 22,0
4x25 RM 0,727 105 132 27,8
4x35 RM 0,524 129 159 30,5
4x35 SM 0,524 129 159 26,4
4x50 SM 0,387 157 188 29,9
4x70 SM 0,268 199 232 33,2
4x95 SM 0,193 246 280 38,6
4x120 SM 0,153 285 318 41,8
4x150 SM 0,124 326 359 46,7
4x185 SM 0,0991 374 406 51,3
4x240 SM 0,0754 445 473 58,3
5x1,5 RE 12,1 18 - 13,7
5x2,5 RE 7,41 26 - 14,8
5x4 RE 4,610 34 46 16,7
5x6 RE 3,080 43 58 18,1
5x10 RE 1,830 59 78 20,6
5x10 RM 1,830 59 78 22,4
5x16 RM/RE 1,150 78 101 25,7
5x25 RM 0,727 105 132 30,3
5x35 RM 0,524 129 159 34,0
5x50 RM 0,387 157 188 38,6
5x70 RM 0,268 199 232 44,1
5x95 RM 0,193 246 280 50,6
5x120 RM 0,153 285 318 52,0
5x35 SM 0,524 129 159 27,6
5x50 SM 0,387 157 188 32,5
5x70 SM 0,268 199 232 37,1
5x95 SM 0,193 246 280 41,1
5x120 SM 0,153 285 318 44,9
5x150 SM 0,124 326 359 49,9
5x185 SM 0,0991 374 406 55,0
5x240 SM 0,0754 445 473 61,6
7x1,5 RE 12,1 18 - 12,8
7x2,5 RE 7,41 26 - 14,0
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W