Installation cable, PVC insulated and sheathed

PFXP-FR

APPLICATION

For fixed installation in open installations and pipes.
Not suitable for installation directly in ground nor directly in concrete without protective ducting.
Not for installations subject to electrical interference.
Direct sunlight (UV) may slightly alter the colour of the sheath.

CERTIFICATES


CONSTRUCTION

  • Sheath
    PVC compound, white or light gray, UV-resistant
  • Bedding
    Extruded elastomere or plastomere compound or plastic tape
  • Conductors
    Cu, class 2 according to EN 60228
  • Insulation
    PVC compound

TEHNICAL CHARACTERISTICS

  • Standard
    NEK 535
  • CPR class
    Eca
  • Test voltage
    2 kV
  • Rated voltage
    300/500 V
  • Bending radius (min)
    6xD
  • Min. laying temperature
    -15°C
  • Max. conductor temperature
    +70°C
  • Max. short-circuit temperature
    +160°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.) Metal weight Cable weight (approx.)
mm2 Ω/km A A mm kg/km kg/km
3x1,5 RM 12,1 18,5 18 10,7 43,2 183
3x2,5 RM 7,41 25 24 11,5 72 232
3x4 RM 4,61 34 30 13,5 115,2 331
3x6 RM 3,08 43 38 15 172,8 436
3x10 RM 1,830 60 50 17,3 288 629
3x16 RM 1,150 80 64 19,6 460,8 884
4x1,5 RM 12,1 18,5 18 11,4 57,6 213
4x2,5 RM 7,41 25 24 12,4 96 274
4x4 RM 4,61 34 30 14,6 153,6 395
4x6 RM 3,08 43 38 16,2 230,4 524
4x10 RM 1,830 60 50 18,7 384 762
4x16 RM 1,150 80 64 21,4 614,4 1081
5x1,5 RM 12,1 18,5 18 12,3 72 246
5x2,5 RM 7,41 25 24 13,4 120 319
5x4 RM 4,61 34 30 16,2 192 483
5x6 RM 3,08 43 38 17,6 288 618
5x10 RM 1,830 60 50 20,3 480 905
5x16 RM 1,150 80 64 23,3 768 1292
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W