Installation cable, XLPE insulated and PVC sheathed

PFXP-LX

APPLICATION

For fixed installation in open installations and pipes.
Not suitable for installation directly in ground nor directly in concrete without protective ducting.
Not for installations subject to electrical interference.
Direct sunlight (UV) may slightly alter the colour of the sheath.

CERTIFICATES


CONSTRUCTION

  • Sheath
    PVC compound, white
  • Bedding
    Extruded elastomere or plastomere compound or plastic tape
  • Conductors
    Cu, class1 or 2 according to EN 60228
  • Insulation
    XLPE compound

TEHNICAL CHARACTERISTICS

  • Standard
    HD 603 S1, IEC 60502-1
  • Test voltage
    2 kV
  • Rated voltage
    300/500 V
  • CPR classification
    Eca
  • Core identification
    Acc. to HD 308 S2
  • Bending radius (min)
    5 x D
  • Max. working temperature
    90°C
  • Min. temp. for cable laying
    -5°C
  • Max. short-circuit temperature
    250°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
3x1,5 RE 12,1 24 31 8,1
4x1,5 RE 12,1 24 31 8,7
5x1,5 RE 12,1 24 31 9,6
3x2,5 RE 7,41 32 40 9,0
4x2,5 RE 7,41 32 40 9,7
5x2,5 RE 7,41 32 40 10,5
3x1,5 RM 12,1 24 31 8,6
4x1,5 RM 12,1 24 31 9,3
5x1,5 RM 12,1 24 31 10,0
3x2,5 RM 7,41 32 40 9,5
4x2,5 RM 7,41 32 40 10,2
5x2,5 RM 7,41 32 40 11,3
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W