SE-N1XE-R; SE-N1XE-U

Power cable 0,6/1 kV with Cu conductors, XLPE insulated and HDPE sheathed

SE-N1XE-R; SE-N1XE-U

APPLICATION

This cable is used as a power distribution cable in power stations, industrial installations and switchgears as well as in local mains. For fixed installation underground, in
interior premises, cable ducts, in the open air, in water - as permitted by the local building regulations - under severe mechanical stressing during installation and
operation.

CONSTRUCTION

  • Sheath
    black or yellow PE compound, UV resistant
  • Bedding
    Extruded elastomere or plastomere compound
  • Conductors
    Cu, class 1 or 2 according to EN 60228
  • Insulation
    XLPE compound DIX 3

TEHNICAL CHARACTERISTICS

  • Standard
    SS 424 14 18, HD 603 S1
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Min.bending radius
    16xD
  • Core identification
    Add. to HD 308 S2
  • Min.laying temperature
    -20°C
  • Max.operating temperature
    90°C
  • Max.short-circuit temperature
    250°C
  • Min.bending radius during installation
    8xD
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
4x10 RE 1,830 74 86 17,7
5x10 RE 1,830 74 86 19,1
4x16 RM 1,150 98 112 19,9
5x16 RM 1,150 98 112 21,5
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W