TFXP (N1XEV-AS/AR)

Power cable 0,6/1 kV with Al conductors, XLPE insulated and HDPE sheathed, with protective PVC outer sheath

TFXP (N1XEV-AS/AR)

APPLICATION

 This cable is used as a power distribution cable in power stations, industrial installations and switchgears as well as in local mains. For fixed installation underground, in interior premises, cable ducts, in the open air, in water - as permitted by the local building regulations - under severe mechanical stressing during installation and operation. 

CONSTRUCTION

  • Sheath
    PVC compound, green color
  • Bedding
    Extruded elastomere or plastomere compound or plastic tape
  • Conductors
    Al, class 1 or class 2 according to EN 60228
  • Insulation
    XLPE compound
  • Inner sheath
    HDPE compound

TEHNICAL CHARACTERISTICS

  • Standard
    HD 603 S1; IEC 60502-1
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Fire properties
    EN 60332-1-2
  • Bending radius (min)
    multi-core - 12D
  • Max. working temperature
    90°C
  • Min. temp. for cable laying
    -5°C
  • Max. short-circuit temperature
    250°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.) Metal weight Cable weight (approx.) Average sheath thickness Average insulation thickness
mm2 Ω/km A A mm kg/km kg/km mm mm
4x25 RM/RE 1,200 102 112 24,5 290 603 1,50/1,40 0,9
4x50 SM/SE 0,641 149 158 31,2 580 1020 1,70/1,40 1,00
4x95 SE/SM 0,320 234 234 39,7 1102 1739 2,00/1,50 1,10
4x150 SE/SM 0,206 311 300 48,6 1740 2606 2,00/1,60 1,40
4x240 SE/SM 0,125 427 398 59,0 2784 3924 2,00/1,80 1,70
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W