U-1000 AR2V Torsade

Power cable 0,6/1 kV with Al conductors, XLPE insulated and PVC sheathed

U-1000 AR2V Torsade

APPLICATION

In earth, ducts, on support brackets, in dry and wet conditions etc., where one does not expect mechanical damages and the cables are not exposed to the mechanical tensile strain. In urban networks, industrial plants, electric power plants and other electricity consumers and for connection of control devices in industry, traffic etc.

CERTIFICATES


CONSTRUCTION

  • Sheath
    PVC compound
  • Conductors
    Al, class 2 according to EN 60228
  • Insulation
    XLPE compound

TEHNICAL CHARACTERISTICS

  • Standard
    NF C32-321, IEC 60502-1
  • CPR class
    Eca
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Min. bending radius
    12D
  • Min. laying temperature
    -5°C
  • Max. working temperature
    90°C
  • Max. short-circuit temperature
    250°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
4x1x50 RM 0,641 154 160 30,9
4x1x70 RM 0,443 198 197 34,8
4x1x95 RM 0,320 241 234 39,4
4x1x120 RM 0,253 280 266 43
4x1x150 RM 0,206 324 300 47,8
4x1x185 RM 0,164 371 337 52,4
4x1x240 RM 0,125 439 388 58,7
4x1x300 RM 0,100 508 440 64,5
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W