Power cable 0,6/1 kV with Al conductors, XLPE insulated and PVC sheathed

U-1000 AR2V

APPLICATION

These cables for energy distribution are suitable for all types of low voltage industrial-type connection, in urban grids, building installations, etc. Particularly suited in cases of high operating temperature and when high resistance to solar radiation and atmospheric agents is required. Good resistance to low temperature
and chemical agents. Can be used without additional mechanical protection in the open air, fixed to walls or in raceways, inside walkways, and in empty in Cable Constructions in general. Can be laid underground with mechanical protection constructed from slabs, tiles, or bricks. They are not recommend to lay this cable in ground flooded for more than two months per year. With appropriate mechanical protection it can be use in areas subject to risk of explosion, but in this case the permitted current load is reduced by 15%. It can be used in ambient temperature down to -25°.RM

CERTIFICATES


CONSTRUCTION

  • Sheath
    PVC compound
  • Bedding
    Extruded elastomere or plastomere compound
  • Conductors
    Al, class 2 according to EN 60228
  • Insulation
    XLPE compound

TEHNICAL CHARACTERISTICS

  • Standard
    NF C32-321, IEC 60502-1
  • CPR class
    Eca
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 KV
  • Core identification
    According to HD 308 S2
  • Bending radius (min)
    multi-core - 12D, single-core - 15D
  • Max. working temperature
    90°C
  • Laying temperature (min.)
    -5°C
  • Max. short-circuit temperature
    250°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
1x16 RM 1,910 84 87 8,7
1x25 RM 1,200 101 111 10,2
1x35 RM 0,868 126 134 11,3
1x50 RM 0,641 154 160 12,8
1x70 RM 0,443 198 197 14,4
1x95 RM 0,320 241 234 16,2
1x120 RM 0,253 280 266 17,8
1x150 RM 0,206 324 300 19,8
1x185 RM 0,164 371 337 21,7
1x240 RM 0,125 439 388 24,3
1x300 RM 0,100 508 440 26,7
1x400 RM 0,0778 663 515 30,4
1x500 RM 0,0605 770 583 33,6
1x630 RM 0,0469 889 662 37,5
1x800 RM 0,0367 1019 776 41,7
1x1000 RM 0,0291 1157 865 46,1
2x10 RM 3,080 67 80 16
2x16 RM 1,910 91 104 18,5
2x25 RM 1,200 108 133 22
2x35 RM 0,868 135 160 24,5
3x10 RM 3,080 58 67 17
3x16 RM 1,910 77 87 19,5
3x25 RM 1,200 97 111 23,5
3x35 RM 0,868 120 134 26
3x50 RM 0,641 146 160 29
3x70 RM 0,443 187 197 34
3x95 RM 0,320 227 234 38,5
3x120 RM 0,253 263 266 42,5
3x150 RM 0,206 304 300 47,5
3x185 RM 0,164 347 337 53
3x240 RM 0,125 409 388 59,5
3x300 RM 0,100 471 440 66
3x50+35 RM 0,641/0,868 146 160 28,9
3x70+50 RM 0,443/0,641 187 197 33,5
3x95+50 RM 0,320/0,641 227 234 36,6
3x120+70 RM 0,253/0,443 263 266 40,7
3x150+70 RM 0,206/0,443 304 300 44,6
3x185+70 RM 0,164/0,443 347 337 52,5
3x240+95 RM 0,125 409 388 54,5
4x10 RM 3,080 58 67 18,5
4x16 RM 1,910 77 87 21
4x25 RM 1,200 97 777 25,5
4x35 RM 0,868 120 134 28,5
4x50 RM 0,641 146 160 32,5
4x70 RM 0,443 187 197 37,5
4x95 RM 0,320 227 234 42,5
4x120 RM 0,253 263 266 47,5
4x150 RM 0,206 304 300 52,5
4x185 RM 0,164 347 337 52,5
4x240 RM 0,125 409 388 59
4x300 RM 0,100 471 440 73,5
5x10 RM 3,080 58 67 20
5x16 RM 1,910 77 87 23
5x25 RM 1,200 97 111 28
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W