U-1000 ARVFV

Armoured power cable 0,6/1 kV with Al conductors, XLPE insulated and PVC sheathed

U-1000 ARVFV

APPLICATION

Distribution power cable for static application, mostly in ground, but also in water, within facilities, in cable canals, in concrete. Used in electric power plants, transformer stations, industrial plants, metropolitan networks and other electric plants. Applied in conditions requiring protection against heavier mechanical damages, but where cables are not exposed to heavier tensile strain.

CONSTRUCTION

  • Armour
    Two galvanized steel tapes (multi-core cables) or two Al tapes (single-core cables)
  • Sheath
    PVC compound
  • Bedding
    Extruded elastomere or plastomere compound or plastic tape
  • Conductors
    Al, class 2 according to EN 60228
  • Insulation
    XLPE compound

TEHNICAL CHARACTERISTICS

  • Standard
    NF C 32-322
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Core identification
    According to HD 308 S2
  • Bending radius (min)
    single-core - 15D; multicore - 12D
  • Max. working temperature
    90°C
  • Min. temp. for cable laying
    -5°C
  • Max. short-circuit temperature
    250°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
1x50 RM 0,641 161 162 16,4
1x70 RM 0,443 204 199 18
1x95 RM 0,320 252 238 19,8
1x120 RM 0,253 295 272 21,4
1x150 RM 0,206 339 305 23,4
1x185 RM 0,164 395 347 25,3
1x240 RM 0,125 472 404 27,9
1x300 RM 0,100 547 457 30,3
1x400 RM 0,0778 643 525 34
3x10 RM 3,080 - - 18
3x16 RM 1,910 - - 19,9
3x25 RM 1,200 97 75 23,2
3x35 RM 0,868 120 90 25,6
3x50 RM 0,641 146 106 30,2
3x70 RM 0,443 187 130 34,5
3x95 RM 0,320 227 154 38,3
3x120 RM 0,253 263 174 42
3x150 RM 0,206 304 197 46,3
3x185 RM 0,164 347 220 50,6
3x240 RM 0,125 409 253 56,7
3x300 RM 0,100 471 286 62,3
4x10 RM 3,080 - - 19,3
4x16 RM 1,910 - - 21,5
4x25 RM 1,200 97 75 25,1
4x35 RM 0,868 120 90 27,8
4x50 RM 0,641 146 106 32,8
4x70 RM 0,443 187 130 37,5
4x95 RM 0,320 227 154 41,7
4x120 RM 0,253 263 174 45,8
4x150 RM 0,206 304 197 51,4
4x185 RM 0,164 347 220 56,2
4x240 RM 0,125 409 253 62,6
5x10 RM 3,080 - - 20,7
5x16 RM 1,910 - - 23,1
5x25 RM 1,200 97 75 27,2
5x35 RM 0,868 120 90 30,2
5x50 RM 0,641 146 106 35,6
5x70 RM 0,443 187 130 40,7
5x95 RM 0,320 227 154 45,4
5x120 RM 0,253 263 174 50
5x150 RM 0,206 304 197 56
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W