LV (0,6/1 kV) power cables with XLPE insulation and PVC sheath

U-1000 R2V

APPLICATION

These cables for energy distribution are suitable for all types of low voltage industrial-type connection, in urban grids, building installations, etc. Particularly suited in cases of high operating temperature and when high resistance to solar radiation and atmospheric agents is required. Good resistance to low temperature
and chemical agents. Can be used without additional mechanical protection in the open air, fixed to walls or in raceways, inside walkways, and in empty in Cable Constructions in general. Can be laid underground with mechanical protection constructed from slabs, tiles, or bricks. They are not recommend to lay this cable in ground flooded for more than two months per year. With appropriate mechanical protection it can be use in areas subject to risk of explosion, but in this case the permitted current load is reduced by 15%. It can be used in ambient temperature down to -25°.

CERTIFICATES


CONSTRUCTION

  • Sheath
    PVC compound
  • Bedding
    Extruded elastomere or plastomere compound or plastic tape
  • Conductors
    Cu, class 1 or 2 according to EN 60228
  • Insulation
    XLPE compound

TEHNICAL CHARACTERISTICS

  • Standard
    NF C32-321, IEC 60502-1
  • CPR class
    Cca - s3,d1,a3
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Core identification
    Acc. to HD 308 S2
  • Bending radius (min)
    multi-core - 12D single-core – 15D
  • Min. laying temperature
    -5°C
  • Max. working temperature
    90°C
  • Max. short-circuit temperature
    250°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
1x4 RE/RM 4,61 45 59 7,2
1x6 RE/RM 3,08 58 74 8,2
1x10 RE/RM 1,830 80 101 9,2
1x16 RM 1,150 107 128 10,5
1x25 RM 0,727 142 18 12,5
1x35 RM 0,524 175 179 13,5
1x50 RM 0,387 212 214 15
1x70 RM 0,268 270 264 17
1x95 RM 0,193 327 317 19
1x120 RM 0,153 379 363 21
1x150 RM 0,124 435 405 23
1x185 RM 0,0991 496 457 25,5
1x240 RM 0,0754 584 529 28,5
1x300 RM 0,0601 665 600 31
1x400 RM 0,0470 779 690 34,5
1x500 RM 0,0366 870 780 38,5
1x630 RM 0,0283 995 880 43
2x4 RE/RM 4,61 45 59 13
2x6 RE/RM 3,08 58 74 14
2x10 RE/RM 1,830 80 101 16
2x16 RM 1,150 107 128 18,5
2x25 RM 0,727 142 162 22
2x35 RM 0,524 175 179 26
3x4 RE/RM 4,61 40 51 13
3x6 RE/RM 3,08 52 64 15
3x10 RE/RM 1,830 71 88 17
3x16 RM RM 1,150 96 111 19,5
3x25 RM 0,727 127 141 23,5
3x25 RM 0,524 157 170 26
3x50 RM 0,387 190 204 29,5
3x70 RM 0,268 242 252 34
3x95 RM 0,193 293 302 38,5
3x120 RM 0,153 339 345 42,5
3x150 RM 0,124 390 386 47,5
3x185 RM 0,0991 444 435 53
3x240 RM 0,0754 522 504 59,5
3x300 RM 0,0601 595 571 66
3x35+25 RM 0,524/0,727 157 170 27,2
3x50+35 RM 0,387/0,524 190 204 31,1
3x70+50 RM 0,268/0,387 242 252 36,2
3x95+50 RM 0,193/0,387 293 302 40,6
3x120+70 RM 0,153/0,268 339 345 45,4
3x150+70 RM 0,124/0,268 390 386 49,5
3x185+70 RM 0,0991/0,268 444 435 54,4
3x240+95 RM 0,0754/0,193 522 504 61,5
4x4 RE/RM 4,61 40 46 14
4x6 RE/RM 3,08 52 58 16
4x10 RE/RM 1,830 71 79 18,5
4x16 RM 1,150 96 100 21
4x25 RM 0,727 127 141 25,5
4x35 RM 0,524 157 170 28,5
4x50 RM 0,387 190 204 32,5
4x70 RM 0,268 242 252 37,5
4x95 RM 0,193 293 302 42,5
4x120 RM 0,153 339 345 47,5
4x150 RM 0,124 390 386 52,5
4x185 RM 0,0991 444 435 59
4x240 RM 0,0754 522 504 66,5
4x300 RM 0,0601 595 571 73,5
5x4 RE/RM 4,61 42 53 15,5
5x6 RE/RM 3,08 52 58 17,5
5x10 RE/RM 1,830 71 79 20
5x16 RM 1,150 96 100 23
5x25 RM 0,727 127 141 27
5x35 RM 0,524 157 170 30,5
5x50 RM 0,387 190 204 34
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W