VG-YMvKasmb Al

Power cable 0,6/1 kV with Al conductors, XLPE insulated and HFFR sheathed

VG-YMvKasmb Al

APPLICATION

A power and control cable for general use in low voltage installations up to 1 kV. Suitable for applications indicated in NEN 1010. Suited for direct burial and above ground, as power cable for mains and distribution boards.

CONSTRUCTION

  • Armour
    Galvanized steel wires armour with copper earth wires and galvanizet steel counter helix tape
  • Conductors
    Cu conductors, class 2 according to EN 60228
  • Insulation
    XLPE compound
  • Inner sheath
    PVC compound
  • Outer sheath
    PVC FR compound

TEHNICAL CHARACTERISTICS

  • Standard
    HD 604 S1, IEC 60502-1
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Core identification
    Acc. to HD 308 S2
  • Min. bending radius
    16D
  • Min. laying temperature
    0°C
  • Max. operating temperature
    90°C
  • Max. short-circuit temperature
    250°C
  • Min. bending radius during installation
    10D
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
3x35/16 SM 0,868 128 136 24,6
3x50/16 SM 0,641 152 159 27
3x70/20 SM 0,443 194 197 31,7
3x95/30 SM 0,320 239 236 34,9
3x120/35 SM 0,253 278 269 38,7
3x150/45 SM 0,206 316 302 43
3x185/60 SM 0,164 365 342 47,9
3x240/75 SM 0,125 430 397 53,3
3x300/95 SM 0,100 506 454 59,2
4x35/16 SM 0,868 128 136 27,2
4x50/16 SM 0,641 152 159 30,3
4x70/20 SM 0,443 194 197 35,4
4x95/30 SM 0,320 239 236 39
4x120/35 SM 0,253 278 269 44,1
4x150/45 SM 0,206 316 302 48
4x185/60 SM 0,164 365 342 53,8
4x240/75 SM 0,125 430 397 59,9
4x300/95 SM 0,100 506 454 66,1
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W