Power cables 0,6/1 kV with XLPE insulation and PVC sheath

YKXS

APPLICATION

In earth, ducts, on support brackets, in dry and wet conditions etc., where one does not expect mechanical damages and the cables are not exposed to the mechanical tensile strain. In urban networks, industrial plants, electric power plants and other electricity consumers and for connection of control devices in industry, traffic etc.

CERTIFICATES


CONSTRUCTION

  • Sheath
    PVC compound
  • Bedding
    Extruded elastomere or plastomere compound or plastic tape
  • Conductors
    Cu rope
  • Insulation
    XLPE compound

TEHNICAL CHARACTERISTICS

  • Standard
    PN-HD 603 S1; VDE 0276-603; IEC 60502-1
  • CPR class
    Eca
  • Test voltage
    4 kV
  • Rated voltage
    0,6/1 kV
  • Core identification
    Acc. to HD 308 S2
  • Bending radius (min)
    Single-core - 15D; multi-core - 12D
  • Max. operating temperature
    90°C
  • Min. temp. for cable laying
    -5°C
  • Max short-circuit temperature
    250°C
Nominal cross-section Conductor construction Max. Resistance at 20°C Current capacity in air Current capacity in earth Outer diam. (approx.)
mm2 Ω/km A A mm
1x4 RE 4,610 44 54 7,6
1x6 RE 3,080 56 67 8,2
1x10 RE 1,830 77 89 8,8
1x10 RM 1,830 77 89 9,3
1x16 RM 1,150 102 115 10,4
1x25 RM 0,727 138 148 12,1
1x35 RM 0,524 170 177 13,2
1x50 RM 0,387 207 209 14,8
1x70 RM 0,268 563 256 16,9
1x95 RM 0,193 325 307 18,9
1x120 RM 0,153 380 349 20,6
1x150 RM 0,124 437 393 22,7
1x185 RM 0,0991 507 445 25,1
1x240 RM 0,0754 604 517 27,8
1x300 RM 0,0601 697 583 30,8
1x400 RM 0,0440 811 663 33,1
1x500 RM 0,0366 940 749 36,6
1x630 RM 0,0283 1083 843 40,5
3x4 RE 4,610 42 52 13,0
3x6 RE 3,080 53 64 13,1
3x10 RE 1,830 74 86 15,4
3x10 RM 1,830 74 86 16,3
3x16 RM 1,150 98 112 18,5
3x25 RM 0,727 133 145 22,7
3x35 RM 0,524 162 174 25,3
3x16/10 RM/RM 1,150/1,830 77 88 19,6
3x25/10 RM/RM 0,727/1,830 98 120 19,6
3x25/16 RM/RM 0,727/1,150 105 132 23,9
3x35/16 RM/RM 0,524/1,150 129 159 26,6
3x35/25 RM/RM 0,524/0,727 134 162 26,6
3x50/25 SM/RM 0,387/0,727 157 188 28,1
3x70/35 SM/RM 0,268/0,524 199 232 32,2
3x70/50 SM/RM 0,268/0,387 199 242 32,2
3x95/50 SM/RM 0,193/0,387 246 280 35,8
3x120/70 SM/RM 0,153/0,268 285 318 40,0
3x150/70 SM/RM 0,124/0,268 326 359 43,9
3x185/95 SM/RM 0,0991/0,193 374 406 48,8
3x240/120 SM/RM 0,0754/0,153 445 473 54,2
3x50/35 SM/SM 0,387/0,524 157 188 26,5
3x70/35 SM/SM 0,268/0,524 199 232 30,2
3x95/50 SM/SM 0,193/0,387 246 280 34,2
3x120/70 SM/SM 0,153/0,268 285 318 36,5
3x150/70 SM/SM 0,124/0,268 326 359 40,8
3x185/95 SM/SM 0,0991/0,193 374 406 46,4
3x240/120 SM/SM 0,0754/0,153 445 473 51,3
4x4 RE 4,610 42 52 13,8
4x6 RE 3,080 53 64 15,0
4x10 RE 1,830 74 86 17,2
4x10 RM 1,830 74 86 18,3
4x16 RM 1,150 98 112 21,0
4x25 RM 0,727 133 145 25,7
4x35 RM 0,524 162 174 28,4
4x35 SM 0,524 162 174 25,2
4x50 SM 0,387 197 206 28,1
4x70 SM 0,268 250 254 32,1
4x95 SM 0,193 308 305 36,0
4x120 SM 0,153 359 348 40,2
4x150 SM 0,124 412 392 44,3
4x185 SM 0,0991 475 444 49,0
4x240 SM 0,0754 564 517 54,8
5x4 RE 4,610 42 52 16,7
5x6 RE 3,080 53 64 18,1
5x10 RE 1,830 74 86 21,3
5x10 RM 1,830 74 86 22,4
5x16 RM 1,150 98 112 25,7
5x25 RM 0,727 133 145 30,3
5x35 RM 0,524 162 174 34,0
5x50 RM 0,387 197 206 36,5
5x70 RM 0,268 250 254 39,9
5x95 RM 0,193 308 305 44,5
  • *Permissible current rating values are according to:
  • - three-phase circut
  • - laying depth of 0,8m for buried cables
  • K=1 - resistivity of the ground equal to 1,0K-m/W
  • K=1,5 - resistivity of the ground equal to 1,5K-m/W